Cable Ferrules Selection Guide

Cable ferrules come in insulated single-entry, double-entry and non-insulated types; collar color shows the cross-section; none on solid conductors.

This guide covers the points to look at when choosing products in the Cable Ferrules category.

Ferrule types and where they are used

Ferrules are not used on solid single-core conductors, since there are no strands to spread out.

How the collar color shows the cross-section

The names of insulated products state the French standard or the German standard. Within the same brand, the barrel and length dimensions of a given cross-section are the same in the two series; what changes is the collar color:

The same colors are used for double-entry ferrules. DIN 46228-4 defines a third color series; in this series, for example, 0,75 mm² is gray and 6 mm² is yellow. When buying replacements, look not only at the color but at the standard and cross-section in the product name.

Barrel length and overall length

In the product data, F shows the length of the metal barrel and L the overall length including the collar. For a 1,5 mm² insulated single-entry ferrule the barrel is 8 mm and the overall length 14 mm; for a 6 mm² ferrule the barrel is 12 mm and the overall length 20 mm. Compare the barrel length with the stripping length given by the terminal block or device manufacturer: a short barrel does not fill the clamping point, and a long barrel protrudes from it.

At the same cross-section the barrel length can vary. The Konsan 2,5 mm² non-insulated ferrule is listed in 8 mm and 12 mm lengths; for the double-entry 2 x 2,5 mm² ferrule the barrel length is 10 mm in the Gwest and Isıso data and 8 mm in the Konsan data.

Crimping and installation points to watch

  1. Strip the conductor to the barrel length; the strands must reach all the way to the end of the barrel, and no bare strands should be left outside the collar. Suitable tools are in the cable stripping tools category.
  2. Crimp the ferrule with pliers whose cross-section range matches. Among the ferrule crimping pliers there are models that press square and hexagonal profiles; the shape of the terminal block entry determines which is suitable.
  3. Soldering the wire end does not replace a ferrule: solder has low compressive strength, changes shape under screw pressure and the connection may loosen.
  4. In spring-type push-in DIN rail terminal blocks, a flexible conductor with a ferrule is inserted by pushing, without a tool.

Order notes

Comparison and selection table

Selection CriterionSingle Insulated Wire FerruleTwin (Double-Entry) Insulated FerruleUninsulated Copper Wire Ferrule
Primary PurposeTerminates a single fine-stranded (Class 5) wireBridges two conductors cleanly into one terminal clampTerminates stranded wire in compact or high-temp terminals
Cross-Section Range0.50 mm² – 50+ mm² (DIN/French color-coded collar)2×0.50 mm² – 2×16 mm² (oval flared insulation sleeve)0.50 mm² – 70+ mm² (tin-plated electrolytic copper)
Barrel Length (L2)8 mm (standard), 10 mm, 12 mm or 18 mm (spring cages)8 mm, 10 mm, 12 mm or 14 mm6 mm – 25 mm matched to terminal stripping length
Key CheckMatch conductor mm² to ferrule collar & crimping dieUse twin ferrule instead of twisting two single ferrulesIdeal where plastic collar will not fit terminal entry

Frequently asked questions

What is the difference between German standard and French standard ferrules?

The difference is in the collar color; within the same brand, the barrel and length dimensions of a given cross-section are the same in the two series. For example, a 1,5 mm² ferrule is black in the French standard and red in the German standard; a 2,5 mm² ferrule is gray in the French standard and blue in the German standard. Since the color is used to tell the cross-section apart at a glance, mixing the two series in the same panel can lead to misreading.

Which color ferrule is used for a 2,5 mm² cable?

The color depends on the series chosen. In the French standard the collar of a 2,5 mm² ferrule is gray, in the German standard it is blue; in the DIN 46228-4 series, 2,5 mm² is also blue. The same colors apply to double-entry 2 x 2,5 mm² ferrules. When buying, look not only at the color but at the cross-section value in the product name, because the same color shows a different cross-section in another series.

When is a double-entry ferrule used?

It is used where two flexible conductors will be connected to the same clamping point, for example when making a jumper from terminal block to terminal block. Because the two conductors are crimped together in a single barrel, the strands do not spread out. A value such as 2 x 1,5 mm² in the product name means two conductors, each of that cross-section. Whether two conductors can be connected to one clamping point is checked from the data of the terminal block or device manufacturer.

Which pliers are used to crimp a ferrule?

A ferrule is crimped with ferrule crimping pliers whose cross-section range matches the ferrule. The store has models that press square and hexagonal profiles; the shape of the terminal block entry determines which profile is suitable. Flat pliers or side cutters do not squeeze the barrel all the way around and the conductor may pull out of the barrel. After crimping, the conductor is pulled lightly to check that it holds.

Can a ferrule be fitted to a single-strand cable?

A ferrule is used to keep the strands at the stripped end of a multi-strand (flexible) conductor from spreading out and breaking under the screw. A single-strand conductor has no strands to spread out, so a ferrule is not needed; the conductor is connected directly to the terminal block. Since the cross-section ranges a terminal block accepts for solid and for stranded conductors may differ, the manufacturer's data should be checked.

Can the wire end be soldered instead of using a ferrule?

Soldering the end of a multi-strand conductor and connecting it to a screw terminal block does not replace a ferrule. Solder has low compressive strength; under screw pressure the soldered end changes shape over time, the connection loosens and contact resistance may increase. A flexible conductor is prepared with a ferrule for a screw terminal block and with a cable lug for a bolted connection; if the terminal block accepts a flexible conductor without a ferrule, this is stated in the manufacturer's data.