Motor Control and Protection Equipment Selection Guide

How to size and coordinate motor protection switches, thermal overload relays, direct-on-line starters, and soft starters under IEC 60947-4-1.

Three-phase induction motors draw 6 to 8 times their rated current during direct-on-line starting and require dedicated protection against overload, phase loss, and short circuits. Motor Control Equipment is sized according to IEC 60947-4-1 based on motor full-load current ($I_n$), utilization category (AC-3), and Type 1 / Type 2 coordination tables.

Core components in an industrial motor feeder

Motor control equipment comparison table

Equipment FamilyStandardPrimary FunctionKey Sizing ParameterCategory Link
Motor control & protection unitsIEC 60947-4-1Thermal overload, phase loss, and feeder coordinationMotor full-load current ($I_n$) adjustment rangeMotor Control Equipment
Direct-on-line & enclosed motor startersIEC 60947-4-1Pre-assembled start/stop switching and overload protectionMotor kW rating at 400 V and coil voltageMotor Starters
Soft startersIEC 60947-4-2Stepless voltage ramp for smooth starting and stoppingMotor current, starts per hour, and internal bypassSoft Starters

Frequently asked questions

How should the thermal overload setting be adjusted for a motor?

For direct-on-line (DOL) feeders, set the dial to the exact full-load current ($I_n$) on the motor nameplate; for a thermal relay placed inside the delta loop of a star-delta starter, set it to $0.58 \times I_n$.

What is the difference between Type 1 and Type 2 coordination?

Under IEC 60947-4-1, Type 1 ensures safety under a short circuit but allows contactor or overload relay damage requiring repair, whereas Type 2 guarantees that the starter remains operational after clearing the fault.