Switchgear Auxiliary and Trip Alarm Contacts Selection Guide

How to choose front-mount and side-mount NO/NC auxiliary contact blocks and fault trip alarm contacts for MCBs, MPCBs, and contactors.

Miniature circuit breakers, residual current devices, motor protection circuit breakers, and power contactors report their switching state and fault trips to control circuits and PLCs through Auxiliary Contacts. Selection requires matching the host device's brand/series, mounting style (front snap-on vs side-mount), and contact configuration (NO / NC).

Status contacts (OF) vs fault trip alarm contacts (SD)

Auxiliary contacts comparison table

Contact Block TypeTypical ArrangementMounting PositionPrimary ApplicationCategory Link
Contactor auxiliary contact block1NO+1NC, 2NO+2NC, 4NOFront clip-on or side-mountLatching circuits, reversing interlocks, and PLC feedbackAuxiliary Contacts
Motor protection switch (MPCB) contact1NO+1NC, 2NOFront under-cover or left/right sideZero-width (front-mount) motor protector status monitoringMotor Protection Switches
MCB / RCCB auxiliary & alarm contact1 CO (OF / SD)Side-mounted on DIN rail (9 mm width)Remote monitoring of critical branch circuit tripsMiniature Circuit Breakers

Frequently asked questions

When is a Normally Open (NO) vs Normally Closed (NC) contact used?

Normally Open (NO, 13-14) contacts are wired in parallel with start pushbuttons for self-holding circuits and run indication; Normally Closed (NC, 21-22) contacts are wired in series with the opposite coil for electrical interlocking.

What is the advantage of front-mounted vs side-mounted auxiliary contacts on MPCBs?

Front-mounted blocks snap directly into the breaker face without adding DIN-rail width, whereas side-mounted blocks add 9 mm of rail width but provide higher contact density and easier wire routing.