Relays Selection Guide

Covers residual current, thermal, protection, timer, automation and reactive power control relays; choose by what the relay measures and its function.

This guide explains what to look at when choosing products in the Relays category.

Which relay is in which category

The word relay is used in electrical equipment for very different devices. This category contains only two switchgear protection groups; the others are in their own categories:

The difference between a residual current relay and a thermal overload relay

The two devices measure different quantities. A residual current relay looks at the sum of the currents passing through the phase and neutral conductors; if the sum deviates from zero, part of the current is leaking to earth. Because it is not concerned with the magnitude of the load current, it does not notice an overloaded motor. A thermal overload relay, on the other hand, monitors the thermal effect of the load current in each phase; the milliampere-level current flowing to earth from a housing with damaged insulation is outside its measuring range.

The ways they open the circuit are also different. A residual current relay isolates the line with its own main contacts and is reset manually. A thermal overload relay has no power contact; its auxiliary contact opens the coil circuit of the contactor, and the contactor stops the motor.

The third difference is in the setting. The threshold of a modular residual current relay is fixed and is chosen together with the product. In a thermal overload relay, the current value is set within the setting range to the motor's nameplate current.

Which device against which fault

Brands in this category

Chint NL1 residual current relays and Tense TAR residual current detection relays are also listed in the residual current group.

Order notes

Products in both subgroups are sold by the piece. Some products are listed with a lead time; the delivery time is confirmed separately for these products. If you have a manufacturer code such as A9R41463, F204 AC-80/0.3 or 3RU2116-1GB0, just type it into the site search.

Protection and Control Relay Types Comparison Table

Relay GroupMonitored / Controlled ParameterAdjustment and Output FormTypical ApplicationCategory Link
Phase Failure & Voltage Monitoring RelayPhase sequence, phase loss, asymmetry, over/undervoltageFixed or adjustable threshold + trip delay · 1 CO / 2 COProtecting motors, elevators, compressors and main incoming panelsVoltage Monitoring Relays
Timer Relay (On-Delay / Off-Delay / Star-Delta)0.1 s – 100 h timing rangeOn-delay, off-delay, flasher, star-delta transitionMotor starting, lighting automation and sequential machine logicTimer Relays
Thermal Overload RelayMotor overload current and phase imbalanceDirect mounting beneath contactor · Class 10A/20Motor winding overload protection in contactor starter assembliesThermal Relays
Liquid Level, Photocell & Thermostat RelayElectrode conductivity, ambient lux, temperatureAdjustable sensitivity · Changeover relay outputSubmersible pump dry-run protection and outdoor lighting controlRelays

Frequently asked questions

Can a thermal overload relay be used instead of a residual current relay?

No. A thermal overload relay responds to the thermal effect of the phase current the motor draws and trips only when the current stays above the setting value for a long time. Earth leakages that are dangerous to people are at the milliampere level, and this current stays far below the setting range of a thermal overload relay. A residual current relay, in turn, does not detect motor overload. For this reason the two protections are not used in place of one another but together, as separate devices.

In which category are digital thermal overload relays listed?

Bimetal thermal overload relays and electronic overload relays such as ABB EF and Schneider Electric LR97D are in the Thermal Overload Relays subcategory. Tense TRM digital thermal overload relays, KON-TER models with a built-in contactor and Entes AKC current relays are listed in the Current Protection Relays category under Protection Relays; the relays in this group can monitor undercurrent as well as overcurrent.

Does a phase protection relay do the same job as a thermal overload relay?

No, one monitors voltage and the other current. A phase protection relay detects phase loss, phase sequence error and voltage imbalance on the mains side, and can also prevent the contactor from pulling in before the motor starts. A thermal overload relay looks at the motor current; it trips on overload and jamming. Phase-loss-sensitive thermal overload relays also protect a motor left on two phases, but they do not detect reversed phase sequence. For this reason the two relays can be used together on the same motor feeder.

Where are a residual current relay and a thermal overload relay connected in a panel?

A residual current relay is fitted on the distribution side at the head of the line or group of lines it will protect, and all phase conductors and the neutral of that line pass through the relay; a single relay can protect several feeders. A thermal overload relay, on the other hand, is separate for each motor: it is connected in series at the contactor output, in the three phases going to the motor, and its auxiliary contact enters the coil circuit of that contactor. The manufacturer's diagram is the basis for connection details.