Schneider Electric C10H32M100 NSX100H ML 2.2 M100 70kA

Schneider Electric C10H32M100 NSX100H ML 2.2 M100 70kA

Schneider Electric C10H32M100 NSX100H ML 2.2 M100 70kA. Technical specifications of this model: Short-Circuit Breaking Capacity: 70kA

Short-Circuit Breaking Capacity70 kA
SeriesComPacT yeni nesil
Product TypeCircuit Breaker
Device ApplicationMotor koruması
Pole Arrangement3P
Protected Pole Configuration3d
Rated Current (In)100 A @ 65 °C
Rated Operational Voltage (Ue)690 V AC 50/60 Hz
Current TypeAC
Mains Frequency50/60 Hz
Suitable for IsolationYes (EN/IEC 60947-2)
Utilization CategoryCategory A
Release TypeMicrologic 2.2 M
Trip Unit TechnologyElektronik
Protection FunctionsLSoI
Control TypeFeed-through
Mounting TypeFixed
Rated Insulation Voltage (Ui)800 V AC 50/60 Hz
Rated Impulse Withstand Voltage (Uimp)8 kV
Mechanical Endurance50000 cycles
Electrical Endurance50000 cycles @ 440 V In/2; 30000 cycles @ 440 V In; 20000 cycles @ 690 V In/2; 10000 cycles @ 690 V In
Power Loss per Pole4.7 W
Mounting SupportBackplate
Mounting PositionYatay ve dikey; Sırtında düz
Top ConnectionFront
Bottom ConnectionFront
Connection Range35 mm
Trip Unit Rating100 A @ 65 °C
Long-Time Pick-up Adjustment Range (Ir)50–100 A
Long-Time Delay Adjustment Type (tr)Fixed
Thermal MemoryAçmadan önce ve sonra 20 dakika
Instantaneous Pick-up Adjustment Type (Ii)Fixed
Instantaneous Pick-up Adjustment Range (Ii)1500 A
Earth Leakage ProtectionNone
Zone Selective Interlocking (ZSI)None
Width105 mm
Height161 mm
Depth86 mm
Product Weight2.05 kg
StandardsEN/IEC 60947-2