Schneider Electric C63F31M500 NSX630F MA500 36kA

Schneider Electric C63F31M500 NSX630F MA500 36kA

Schneider Electric C63F31M500 NSX630F MA500 36kA. Technical specifications of this model: Short-Circuit Breaking Capacity: 36kA

Short-Circuit Breaking Capacity36 kA
SeriesComPacT yeni nesil
Product TypeCircuit Breaker
Device ApplicationMotor koruması
Pole Arrangement3P
Protected Pole Configuration3d
Rated Current (In)500 A @ 65 °C
Rated Operational Voltage (Ue)690 V AC 50/60 Hz
Current TypeAC
Mains Frequency50/60 Hz
Suitable for IsolationYes (EN/IEC 60947-2)
Utilization CategoryCategory A
Release TypeMicrologic 1.3 M
Trip Unit TechnologyElektronik
Protection FunctionsSI
Control TypeFeed-through
Mounting TypeFixed
Rated Insulation Voltage (Ui)800 V AC 50/60 Hz
Rated Impulse Withstand Voltage (Uimp)8 kV
Mechanical Endurance15000 cycles
Electrical Endurance8000 cycles @ 440 V In/2; 4000 cycles @ 440 V In; 6000 cycles @ 690 V In/2; 2000 cycles @ 690 V In
Power Loss per Pole25 W
Mounting SupportBackplate
Mounting PositionYatay ve dikey; Sırtında düz
Top ConnectionFront
Bottom ConnectionFront
Connection Range45 mm
Trip Unit Rating500 A @ 65 °C
Instantaneous Pick-up Adjustment Type (Ii)Fixed
Instantaneous Pick-up Adjustment Range (Ii)6500 A
Earth Leakage ProtectionNone
Zone Selective Interlocking (ZSI)None
Width140 mm
Height255 mm
Depth110 mm
Product Weight6.2 kg
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electric Shock Protection ClassSınıf II üzerinde ön yüz
Pollution Degree3 (IEC 60664-1)