Schneider Electric C63F32D630 NSX630F Micrologic 2.3 36kA

Schneider Electric C63F32D630 NSX630F Micrologic 2.3 36kA

Schneider Electric C63F32D630 NSX630F Micrologic 2.3 36kA. Technical specifications of this model: Short-Circuit Breaking Capacity: 36kA

Short-Circuit Breaking Capacity36 kA
SeriesComPacT yeni nesil
Product TypeCircuit Breaker
Device ApplicationDistribution
Pole Arrangement3P
Protected Pole Configuration3d
Rated Current (In)630 A @ 40 °C
Rated Operational Voltage (Ue)690 V AC 50/60 Hz
Current TypeAC
Mains Frequency50/60 Hz
Suitable for IsolationYes (EN/IEC 60947-2)
Utilization CategoryCategory A
Release TypeMicrologic 2.3
Trip Unit TechnologyElektronik
Protection FunctionsLSoI
Control TypeFeed-through
Mounting TypeFixed
Rated Insulation Voltage (Ui)800 V AC 50/60 Hz
Rated Impulse Withstand Voltage (Uimp)8 kV
Mechanical Endurance15000 cycles
Electrical Endurance8000 cycles @ 440 V In/2; 4000 cycles @ 440 V In; 6000 cycles @ 690 V In/2; 2000 cycles @ 690 V In
Power Loss per Pole39.7 W
Mounting SupportBackplate
Mounting PositionYatay ve dikey; Sırtında düz
Top ConnectionFront
Bottom ConnectionFront
Connection Range45 mm
Trip Unit Rating630 A @ 40 °C
Long-Time Pick-up Adjustment Range (Ir)250–630 A
Long-Time Delay Adjustment Type (tr)Fixed
Thermal MemoryAçmadan önce ve sonra 20 dakika
Instantaneous Pick-up Adjustment Type (Ii)Fixed
Instantaneous Pick-up Adjustment Range (Ii)6900 A
Earth Leakage ProtectionNone
Zone Selective Interlocking (ZSI)None
Width140 mm
Height255 mm
Depth110 mm
Product Weight6.2 kg
StandardsEN/IEC 60947-2