Clamp Meters Selection Guide

Clamp meters are divided into AC-only, AC/DC, fork, flexible-clamp and leakage current types; selection looks at criteria such as the current range.

This guide explains what to look at when choosing products in the Clamp Meters category.

Clamp meter types

What to look at when choosing a clamp meter

  1. Current range. The value in the product name (such as 400 A, 600 A, 1000 A) is the highest range and must cover the largest expected current. For small currents the lower ranges are decisive; the data of some models lists the 3 A and 30 A ranges separately with their own accuracy values.
  2. Jaw opening. The outer diameter of a single core or the width of a busbar must fit in the jaw. The product data includes values such as 17 mm for mini models, 28 mm and 30 mm for 400 A and 600 A models, and 42 mm, 63 mm and 75 mm for high-current models.
  3. True RMS. The current of non-linear loads such as variable frequency drives, electronic ballasts and computers is not sinusoidal; a clamp that works on the average value reads this current incorrectly, so a True RMS model is chosen for these loads. If voltage will also be measured at the drive output, look for the VFC or low-pass filter (LPF) function in the data.
  4. Accuracy and display count. Accuracy is written in the form ±(2%+5), as a percentage of the reading and a count margin on the last digit; because the count margin is fixed, the relative error of a small current on the same range increases. The display count appears in the data with values such as 6000, 4000, 2000 and 9999.
  5. Measurement category. The data includes values such as CAT III 600 V and CAT III 1000 V / CAT IV 600 V. Measurements at the distribution board and in fixed installations fall under CAT III, and measurements at the meter and on the main overcurrent protection side fall under CAT IV; the required class is determined according to the project and manufacturer data.
  6. Additional measurements. Inrush measurement for motor starting current, non-contact voltage detection (NCV), a low-impedance voltage range (LoZ), temperature, capacitance and Bluetooth connectivity vary by model.
  7. Supply. The battery size is written in the data with an IEC code: R03 is the AAA battery, R6 and LR6 are the AA battery, and 6F22 is the 9 V battery size.

Points to watch for a correct reading

To compare the measured current with the value expected from the rated power on the load's label, you can use the active power to current and fuse calculation tool.

Measuring instruments that look similar

Brand and order notes

Comparison and selection table

Selection CriterionStandard AC Clamp MeterAC / DC True RMS Clamp MeterLeakage Current (mA) / Flexible Rogowski Clamp
Current CapabilityAC current only (400 A – 1000 A)Both AC and DC current (400 A – 1000 A Hall-effect sensor)Micro-resolution mA leakage (0.01 mA) or flexible coil (3000 A)
Waveform AccuracyAverage-responding or True RMS modelsTrue RMS (accurate on distorted VFD & non-linear loads)True RMS with low-pass filter or flexible loop for tight busbars
Jaw & Extra Functions25–40 mm jaw; AC/DC voltage, resistance, continuityDC Zero button, motor Inrush capture, capacitance, HzEarth leakage diagnostics or wrapping around multi-cable bundles
Typical ApplicationGeneral building maintenance, AC motors & PFC panelsSolar PV strings, battery banks, UPS, automotive & VFDsTroubleshooting nuisance RCD trips & heavy busbar risers

Frequently asked questions

Does a clamp meter measure DC current?

Not every model does. Clamps that work on the current transformer principle measure only alternating current. For direct current you need models that use a Hall-effect sensor and state AC/DC and DC current measurement in the name or data. If you will measure on a battery, solar panel or DC drive circuit, check that the product data includes a DC current range.

How is ±(2%+5) accuracy interpreted?

The first number is a percentage of the reading, and the second number is the count margin on the last digit of the display. For a reading of 100.0 A at 0.1 A resolution, the 2% margin is 2.0 A and 5 counts equal 0.5 A; the true value can be between 97.5 A and 102.5 A. When 5.0 A is read on the same range, the margin is 0.6 A, so the relative error grows noticeably.

How are small currents measured with a clamp meter?

For small currents, the resolution of high-range clamps may be insufficient. If the conductor is passed through the jaw several times, the reading is multiplied by the number of turns; the true current is found by dividing the reading by the number of turns, although accuracy drops somewhat. For continuous small-current measurement, low-range mini models or a multimeter connected in series with the circuit are more suitable. For leakage currents at the milliampere level, leakage current clamps are listed in this category.

What is inrush current measurement used for?

Loads such as motors and transformers draw a short-term current above their continuous operating current at the moment they are switched on. The normal measurement mode cannot capture this brief peak value. Clamps with an inrush function capture the initial current and hold it on the display. This value is used to investigate protective devices that trip during starting and starting problems.

Is a clamp-type earth tester the same as a clamp meter?

No. Although they look alike, a clamp-type earth tester measures the resistance of the earthing loop in ohms through the earthing conductor it grips. A clamp meter, on the other hand, shows the current passing through the conductor in amperes. Some earth testers can also show leakage current, but a clamp meter cannot measure earth resistance. Earth testers are listed in the earthing measuring instruments category.