What is the difference between an MCB and an MCCB?

Compare MCB and MCCB circuit breakers across rated current, short-circuit breaking capacity, adjustable trip units and panel mounting.

What is the main difference between an MCB and an MCCB? A miniature circuit breaker (MCB) is a modular DIN-rail device for final sub-circuits up to 125 A with fixed B, C or D tripping curves; a molded case circuit breaker (MCCB) covers 16 A to 1600 A with higher breaking capacities (16 kA – 150 kA) and adjustable thermal-magnetic or electronic trip units for main distribution feeders.

MCB vs MCCB comparison table

CriterionMiniature Circuit Breaker (MCB)Molded Case Circuit Breaker (MCCB)
Governing StandardIEC/EN 60898-1 and IEC/EN 60947-2IEC/EN 60947-2
Rated Current (In)0.5 A – 125 A (typically 6 A – 63 A)16 A – 1600 A
Breaking Capacity3 kA, 4.5 kA, 6 kA, 10 kA16 kA, 25 kA, 36 kA, 50 kA, 70 kA+ (Icu / Ics)
Trip SettingsFixed factory curve (B, C, D)Fixed, adjustable thermal-magnetic, or electronic trip unit
Mounting35 mm DIN rail clip-onBackplate bolt-on, busbar or plug-in/withdrawable
Category LinkMiniature Circuit BreakersMolded Case Circuit Breakers

Frequently asked questions

When should I choose an MCCB instead of an MCB between 63 A and 125 A?

Choose an MCCB when prospective fault current exceeds 10 kA, when upstream selectivity requires adjustable thermal/magnetic settings, or when terminating heavy feeder cables with lugs.