Cable Current-Carrying Capacity Calculator
Cross-section alone is not enough. The same cross-section carries a different current depending on insulation, installation method, ambient temperature and the number of circuits running side by side.
Formula used
Corrected capacity: Iz = Iz₀ × k₁ × k₂
Copper cable current-carrying capacity table · PVC insulation (70 °C)
IEC 60364-5-52 reference values: 30 °C ambient temperature, single circuit, amperes. B2 describes a multi-core cable in conduit or trunking on a wall, C a cable fixed directly to the wall surface; values are lower in conduit inside a thermally insulated wall.
| Cross-section (mm²) | B2 · 2 loaded conductors | B2 · 3 loaded conductors | C · 2 loaded conductors | C · 3 loaded conductors |
|---|---|---|---|---|
| 1.5 | 16.5 | 15 | 19.5 | 17.5 |
| 2.5 | 23 | 20 | 27 | 24 |
| 4 | 30 | 27 | 36 | 32 |
| 6 | 38 | 34 | 46 | 41 |
| 10 | 52 | 46 | 63 | 57 |
| 16 | 69 | 62 | 85 | 76 |
| 25 | 90 | 80 | 112 | 96 |
| 35 | 111 | 99 | 138 | 119 |
| 50 | 133 | 118 | 168 | 144 |
| 70 | 168 | 149 | 213 | 184 |
| 95 | 201 | 179 | 258 | 223 |
| 120 | 232 | 206 | 299 | 259 |
| 150 | 258 | 225 | 344 | 299 |
| 185 | 294 | 255 | 392 | 341 |
| 240 | 344 | 297 | 461 | 403 |
| 300 | 394 | 339 | 530 | 464 |
Copper cable current-carrying capacity table · XLPE insulation (90 °C)
IEC 60364-5-52 reference values: 30 °C ambient temperature, single circuit, amperes. B2 describes a multi-core cable in conduit or trunking on a wall, C a cable fixed directly to the wall surface; values are lower in conduit inside a thermally insulated wall.
| Cross-section (mm²) | B2 · 2 loaded conductors | B2 · 3 loaded conductors | C · 2 loaded conductors | C · 3 loaded conductors |
|---|---|---|---|---|
| 1.5 | 22 | 19.5 | 24 | 22 |
| 2.5 | 30 | 26 | 33 | 30 |
| 4 | 40 | 35 | 45 | 40 |
| 6 | 51 | 44 | 58 | 52 |
| 10 | 69 | 60 | 80 | 71 |
| 16 | 91 | 80 | 107 | 96 |
| 25 | 119 | 105 | 138 | 119 |
| 35 | 146 | 128 | 171 | 147 |
| 50 | 175 | 154 | 209 | 179 |
| 70 | 221 | 194 | 269 | 229 |
| 95 | 265 | 233 | 328 | 278 |
| 120 | 305 | 268 | 382 | 322 |
| 150 | 334 | 300 | 441 | 371 |
| 185 | 384 | 340 | 506 | 424 |
| 240 | 459 | 398 | 599 | 500 |
| 300 | 532 | 455 | 693 | 576 |
Aluminum cable current-carrying capacity table · PVC insulation (70 °C)
IEC 60364-5-52 reference values: 30 °C ambient temperature, single circuit, amperes. B2 describes a multi-core cable in conduit or trunking on a wall, C a cable fixed directly to the wall surface; values are lower in conduit inside a thermally insulated wall. The standard also gives smaller aluminum cross-sections; 25 mm² and above are shown here.
| Cross-section (mm²) | B2 · 2 loaded conductors | B2 · 3 loaded conductors | C · 2 loaded conductors | C · 3 loaded conductors |
|---|---|---|---|---|
| 25 | 71 | 62 | 83 | 73 |
| 35 | 86 | 77 | 103 | 90 |
| 50 | 104 | 92 | 125 | 110 |
| 70 | 131 | 116 | 160 | 140 |
| 95 | 157 | 139 | 195 | 170 |
| 120 | 181 | 160 | 226 | 197 |
| 150 | 201 | 176 | 261 | 227 |
| 185 | 230 | 199 | 298 | 259 |
| 240 | 269 | 232 | 352 | 305 |
| 300 | 308 | 265 | 406 | 351 |
Aluminum cable current-carrying capacity table · XLPE insulation (90 °C)
IEC 60364-5-52 reference values: 30 °C ambient temperature, single circuit, amperes. B2 describes a multi-core cable in conduit or trunking on a wall, C a cable fixed directly to the wall surface; values are lower in conduit inside a thermally insulated wall. The standard also gives smaller aluminum cross-sections; 25 mm² and above are shown here.
| Cross-section (mm²) | B2 · 2 loaded conductors | B2 · 3 loaded conductors | C · 2 loaded conductors | C · 3 loaded conductors |
|---|---|---|---|---|
| 25 | 94 | 84 | 101 | 90 |
| 35 | 115 | 103 | 126 | 112 |
| 50 | 138 | 124 | 154 | 136 |
| 70 | 175 | 156 | 198 | 174 |
| 95 | 210 | 188 | 241 | 211 |
| 120 | 242 | 216 | 280 | 245 |
| 150 | 261 | 240 | 324 | 283 |
| 185 | 300 | 272 | 371 | 323 |
| 240 | 358 | 318 | 439 | 382 |
| 300 | 415 | 364 | 508 | 440 |
Ambient temperature correction factor (k₁)
The reference is 30 °C; at a different ambient temperature the table value is multiplied by this factor.
| Ambient temperature | PVC · 70 °C | XLPE · 90 °C |
|---|---|---|
| 25 °C | 1.06 | 1.04 |
| 30 °C | 1.00 | 1.00 |
| 35 °C | 0.94 | 0.96 |
| 40 °C | 0.87 | 0.91 |
| 45 °C | 0.79 | 0.87 |
| 50 °C | 0.71 | 0.82 |
Grouping correction factor (k₂)
Applied by the number of equally loaded circuits of the same type laid together. For cables bunched on a surface, the factors in the bunched column also apply.
| Number of circuits | Bunched · in conduit/trunking (B2) | Single layer, side by side · on a surface (C) |
|---|---|---|
| 1 | 1.00 | 1.00 |
| 2 | 0.80 | 0.85 |
| 3 | 0.70 | 0.79 |
| 4 | 0.65 | 0.75 |
Example: 2.5 mm² copper cable, 35 °C ambient, two circuits
- Table value: for a PVC-insulated 2.5 mm² copper cable, method B2, 3 loaded conductors, Iz₀ = 20 A.
- Correction: k₁ = 0.94 for 35 °C and k₂ = 0.80 for two circuits; total factor 0.752.
- Result: Iz = 20 × 0.752 = 15.04 A.
How many amps does a 1.5 mm² cable carry?
For a PVC-insulated 1.5 mm² multi-core copper cable at 30 °C ambient and a single circuit, the reference current in conduit or trunking (B2) is 15 A for a three-phase circuit (3 loaded conductors) and 16.5 A for a single-phase circuit (2 loaded conductors); laid on a wall surface (C) it is 17.5 A and 19.5 A respectively. With XLPE insulation, the same order reads 19.5 A, 22 A, 22 A and 24 A. Ambient temperatures above 30 °C and the number of circuits laid together lower these values; the protective device is selected separately.
How many amps does a 2.5 mm² cable carry?
For a PVC-insulated 2.5 mm² multi-core copper cable at 30 °C ambient and a single circuit, the reference current in conduit or trunking (B2) is 20 A for a three-phase circuit (3 loaded conductors) and 23 A for a single-phase circuit (2 loaded conductors); laid on a wall surface (C) it is 24 A and 27 A respectively. With XLPE insulation, the same order reads 26 A, 30 A, 30 A and 33 A. Ambient temperatures above 30 °C and the number of circuits laid together lower these values; the protective device is selected separately.
How many amps does a 4 mm² cable carry?
For a PVC-insulated 4 mm² multi-core copper cable at 30 °C ambient and a single circuit, the reference current in conduit or trunking (B2) is 27 A for a three-phase circuit (3 loaded conductors) and 30 A for a single-phase circuit (2 loaded conductors); laid on a wall surface (C) it is 32 A and 36 A respectively. With XLPE insulation, the same order reads 35 A, 40 A, 40 A and 45 A. Ambient temperatures above 30 °C and the number of circuits laid together lower these values; the protective device is selected separately.
How many amps does a 6 mm² cable carry?
For a PVC-insulated 6 mm² multi-core copper cable at 30 °C ambient and a single circuit, the reference current in conduit or trunking (B2) is 34 A for a three-phase circuit (3 loaded conductors) and 38 A for a single-phase circuit (2 loaded conductors); laid on a wall surface (C) it is 41 A and 46 A respectively. With XLPE insulation, the same order reads 44 A, 51 A, 52 A and 58 A. Ambient temperatures above 30 °C and the number of circuits laid together lower these values; the protective device is selected separately.
Which conditions change cable capacity?
The same cross-section carries a different current depending on PVC or XLPE insulation, surface or conduit/trunking installation, the number of loaded conductors, ambient temperature and the number of circuits side by side.
Is it enough for choosing the cross-section?
Current-carrying capacity is only the thermal criterion. Voltage drop, short-circuit withstand, protection coordination, harmonics and mechanical conditions must also be checked for the final cross-section.