Entes ENT.CXD.H-400-30 Three-Phase Low Voltage Power Capacitor, 30kVAr, 400VAC

Entes ENT.CXD.H-400-30 Three-Phase Low Voltage Power Capacitor, 30kVAr, 400VAC

Entes ENT.CXD.H-400-30 Three-Phase Low Voltage Power Capacitor, 30kVAr, 400VAC. Three-Phase Power Capacitors are used in staged or fixed reactive power correction in Power Factor Correction panels. Technical values: Size Type 116x255mm, Voltage 400VAC. Stock code: M5026.

Size Type116x255mm
Voltage400 V AC
Operating Frequency50/60 Hz
Capacitance Tolerance%-5+%10
Dielectric Losses≤0,2 W/kVAr
Test Voltage (Terminal-Terminal)2,15 x Un, AC 2 s
Test Voltage (Terminal-Case)3 kV, AC 10 s
Maximum Permissible Voltage1,1xUn
IP RatingIP20
StandardsIEC 60831-1/2
Operating Temperature-25+55°C
Capacitance3x199 µF
Rated Current (In)43.3 A