Cables Selection Guide

Cables are divided into power, control and signal, fire, data and communication groups by the job they carry out; selection depends on the function of the line.

This guide explains what to look at when choosing products in the Cables category.

Cable groups and which one suits which job

The subgroups are divided by what the line carries.

What to look at when choosing a cable, in order

  1. Rated voltage. Building installation cables are in the 300/500 V or 450/750 V class, and underground power cables in the 0.6/1 kV class; the cable's class must meet the system voltage.
  2. Conductor. In fixed installations a solid or stranded rigid conductor is used; inside panels and in moving connections a fine-stranded flexible conductor is used. An aluminum conductor requires a larger cross-section than copper for the same current.
  3. Cross-section and number of cores. The current a cross-section can carry varies with the installation method, the ambient temperature and the number of circuits running side by side; on long lines the voltage drop often determines the cross-section. For a pre-check you can use the cable current carrying capacity calculation and voltage drop calculation tools; the exact value belongs to the project calculation. All of the steps are in the how to select a cable guide.
  4. Insulation and sheath. PVC is a general-purpose material. XLPE insulation allows a higher conductor temperature: in HES datasheets the maximum operating temperature is 70 °C for PVC-insulated NYY and 90 °C for XLPE-insulated N2XH. Halogen-free compounds give off little smoke and little corrosive gas in a fire. Types with PUR sheaths are chosen against oil and abrasion, and types with silicone insulation for high temperature.
  5. Shielding. Shielded types are used against electrical noise on motor outputs with frequency converters and on measurement and communication lines; in the code, C indicates a copper shield and (St) a foil shield.
  6. Installation environment. Underground, outdoors, a damp space, a cable tray or a moving machine: the place of use for each type is stated in the manufacturer's datasheet.

How to read the type code and cross-section notation

In product names, the harmonized code, the German standard code and their Turkish equivalents can appear side by side.

Halogen-free cable and fire-resistant cable are not the same

The term halogen-free (halogen free, LSZH, HFFR) describes that the cable gives off little smoke and little corrosive gas while burning. Fire resistance, on the other hand, means the cable keeps the circuit working for a specified time under flame, and is indicated in product names with suffixes such as FE180, PH120 and E30. Expressions such as B2ca-s1a,d1,a1 indicate a third property, the reaction to fire class: after the main class, s is the smoke, d the flaming droplets while burning, and a the acidity additional class. Which one is required in fire detection, emergency lighting and evacuation systems is determined by the project and the fire regulation. The details are in the article is halogen-free cable fire-resistant.

Brands in this category

In power cables, products from Nexans, HES, Prysmian, Koç, Öznur and Ünal predominate; in control, signal, fire and data cables, products from Reçber, Birtaş and Mekas predominate. Ready-made connection cables with plugs are listed under the Bylion brand.

Order notes

Cable Main Groups and Application Comparison Table

Cable GroupRepresentative Cable TypesVoltage and ConstructionTypical ApplicationCategory Link
Low-Voltage Power CablesNYA, NYAF, NYM, TTR, NYY, N2XH300/500 V – 0.6/1 kV · Cu / AlBuilding wiring, panel feeders, underground and industrial power distributionLow-Voltage Cables
Low-Current, Control & Signal CablesYSLY (JZ/OZ), LIYCY, LIHCH, Cat6, J-Y(St)Y300/500 V · Shielded / unshielded multi-coreIndustrial automation, PLC signaling, machine control and data networksLow-Current Cables
Fire-Resistant & Halogen-Free CablesNHXMH, N2XH, JE-H(St)H FE180/PH120LSZH (Low smoke zero halogen) · FE180Hospitals, malls, tunnels, fire alarm and emergency life-safety circuitsFire Cables
Special, Solar & Silicone CablesH1Z2Z2-K (Solar), H05SS-F (Silicone), Flat CraneUV, ozone and +180 °C heat resistantSolar PV plants, industrial ovens/furnaces and overhead crane festoonsSpecial Cables

Frequently asked questions

Where can I find the cable outer diameter and weight per meter?

Outer diameter and weight are not a single fixed value; they are approximate values that vary slightly by manufacturer and are given per cross-section in the manufacturer's datasheet. For example, the HES datasheet gives an outer diameter of about 10.5 mm and a weight of 180 kg/km for 3x2.5 mm² NYM. For gland, conduit and cable trunking dimensions and for reel weight calculations, the datasheet of the brand purchased is the basis.

What is the difference between NYA, NYAF, NYM, NYY and TTR?

NYA and NYAF are unsheathed single-core cables with a rigid and a fine-stranded conductor respectively; they are used inside conduit, trunking or panels. NYM (antigron) is a sheathed multicore cable for fixed installation inside buildings. NYY is a power cable in the 0.6/1 kV class, laid underground and in cable trunking. TTR (H05VV-F) is a sheathed flexible cable with a fine-stranded conductor and is used for portable device connections.

When is a shielded cable needed?

When the signal must be protected from external noise, or when the cable must be prevented from spreading noise to its surroundings. Typical examples are the power cable between a frequency converter and a motor, analog measurement signals, encoders and communication lines. Among control cables, YSLY is unshielded and YSLCY is shielded; among signal cables, LIYY is unshielded and LIYCY is shielded. How the shield is grounded is determined by the device manufacturer's instructions.

In what order is the cable cross-section determined?

First the load current of the circuit is calculated. Then it is checked that the current the cable can carry with that installation method, at the ambient temperature and together with the neighboring circuits meets the load current. The third step is the voltage drop according to line length; on long lines this mostly determines the cross-section. Finally, short-circuit withstand strength and compatibility with the protective device are verified. The exact cross-section is given by the project calculation.

What changes if a cable with aluminum conductors is chosen instead of copper?

The conductivity of aluminum is lower than that of copper; in HES datasheets the DC resistance of a 16 mm² conductor at 20 °C is given as 1.15 Ω/km for copper and 1.91 Ω/km for aluminum. For this reason a larger cross-section is needed for the same current, though the cable still stays lighter. Cable lugs suitable for aluminum, or bimetallic ones, are used in the connections. The aluminum-conductor NAYY and NA2XH types are under low voltage cables.