Busbar Current-Carrying Capacity Calculator
For busbar selection in panels and distribution systems, correct the DIN 43671 (copper) and DIN 43670 (aluminum) continuous current values for ambient and busbar temperature.
Formula used
Continuous current: I = I₀ × (Δθ / 30)^0.61 × √(R₆₅ / R)
Copper busbar current-carrying capacity table · bare (DIN 43671)
Indoors, free air, alternating current up to 60 Hz; wide face of the bar vertical, spacing between parallel bars equal to the bar thickness; continuous current (A) at 35 °C ambient and 65 °C busbar temperature. The value drops with the wide face horizontal. Columns are the number of parallel bars per phase; arrangements without a table value are shown as “–”.
| Size (mm) | 1 bar | 2 bars | 3 bars | 4 bars |
|---|---|---|---|---|
| 20×5 | 274 | 500 | 690 | – |
| 20×10 | 427 | 825 | 1180 | – |
| 30×5 | 379 | 672 | 896 | – |
| 30×10 | 573 | 1060 | 1480 | – |
| 40×5 | 482 | 836 | 1090 | – |
| 40×10 | 715 | 1290 | 1770 | 2280 |
| 50×5 | 583 | 994 | 1240 | 1920 |
| 50×10 | 852 | 1510 | 2040 | 2600 |
| 60×5 | 688 | 1150 | 1440 | 2210 |
| 60×10 | 985 | 1720 | 2300 | 2900 |
| 80×5 | 885 | 1450 | 1750 | 2720 |
| 80×10 | 1240 | 2110 | 2790 | 3450 |
| 100×5 | 1080 | 1730 | 2050 | 3190 |
| 100×10 | 1490 | 2480 | 3260 | 3980 |
| 120×10 | 1740 | 2860 | 3740 | 4500 |
| 160×10 | 2220 | 3590 | 4680 | 5530 |
| 200×10 | 2690 | 4310 | 5610 | 6540 |
Copper busbar current-carrying capacity table · painted (DIN 43671)
Indoors, free air, alternating current up to 60 Hz; wide face of the bar vertical, spacing between parallel bars equal to the bar thickness; continuous current (A) at 35 °C ambient and 65 °C busbar temperature. The value drops with the wide face horizontal. Columns are the number of parallel bars per phase; arrangements without a table value are shown as “–”.
| Size (mm) | 1 bar | 2 bars | 3 bars | 4 bars |
|---|---|---|---|---|
| 20×5 | 319 | 560 | 728 | – |
| 20×10 | 497 | 924 | 1320 | – |
| 30×5 | 447 | 760 | 944 | – |
| 30×10 | 676 | 1200 | 1670 | – |
| 40×5 | 573 | 952 | 1140 | – |
| 40×10 | 850 | 1470 | 2000 | 2580 |
| 50×5 | 697 | 1140 | 1330 | 2010 |
| 50×10 | 1020 | 1720 | 2320 | 2950 |
| 60×5 | 826 | 1330 | 1510 | 2310 |
| 60×10 | 1180 | 1960 | 2610 | 3290 |
| 80×5 | 1070 | 1680 | 1830 | 2830 |
| 80×10 | 1500 | 2410 | 3170 | 3930 |
| 100×5 | 1300 | 2010 | 2150 | 3300 |
| 100×10 | 1810 | 2850 | 3720 | 4530 |
| 120×10 | 2110 | 3280 | 4270 | 5130 |
| 160×10 | 2700 | 4130 | 5360 | 6320 |
| 200×10 | 3290 | 4970 | 6430 | 7490 |
Aluminum busbar current-carrying capacity table · bare (DIN 43670)
Indoors, free air, alternating current up to 60 Hz; wide face of the bar vertical, spacing between parallel bars equal to the bar thickness; continuous current (A) at 35 °C ambient and 65 °C busbar temperature. The value drops with the wide face horizontal. Columns are the number of parallel bars per phase; arrangements without a table value are shown as “–”.
| Size (mm) | 1 bar | 2 bars | 3 bars | 4 bars |
|---|---|---|---|---|
| 20×5 | 214 | 392 | 537 | – |
| 20×10 | 331 | 643 | 942 | – |
| 30×5 | 295 | 526 | 699 | – |
| 30×10 | 445 | 832 | 1200 | – |
| 40×5 | 376 | 658 | 851 | – |
| 40×10 | 557 | 1030 | 1460 | 1900 |
| 50×5 | 455 | 786 | 995 | 1520 |
| 50×10 | 667 | 1210 | 1710 | 2210 |
| 60×5 | 533 | 910 | 1130 | 1750 |
| 60×10 | 774 | 1390 | 1940 | 2480 |
| 80×5 | 688 | 1150 | 1400 | 2180 |
| 80×10 | 983 | 1720 | 2380 | 2990 |
| 100×5 | 846 | 1390 | 1660 | 2580 |
| 100×10 | 1190 | 2050 | 2790 | 3470 |
| 120×10 | 1390 | 2360 | 3200 | 3930 |
| 160×10 | 1780 | 2960 | 4000 | 4820 |
| 200×10 | 2160 | 3560 | 4790 | 5710 |
Aluminum busbar current-carrying capacity table · painted (DIN 43670)
Indoors, free air, alternating current up to 60 Hz; wide face of the bar vertical, spacing between parallel bars equal to the bar thickness; continuous current (A) at 35 °C ambient and 65 °C busbar temperature. The value drops with the wide face horizontal. Columns are the number of parallel bars per phase; arrangements without a table value are shown as “–”.
| Size (mm) | 1 bar | 2 bars | 3 bars | 4 bars |
|---|---|---|---|---|
| 20×5 | 254 | 446 | 570 | – |
| 20×10 | 393 | 730 | 1060 | – |
| 30×5 | 356 | 606 | 739 | – |
| 30×10 | 536 | 956 | 1340 | – |
| 40×5 | 456 | 762 | 898 | – |
| 40×10 | 677 | 1180 | 1650 | 2190 |
| 50×5 | 556 | 916 | 1050 | 1580 |
| 50×10 | 815 | 1400 | 1940 | 2540 |
| 60×5 | 655 | 1070 | 1190 | 1820 |
| 60×10 | 951 | 1610 | 2200 | 2870 |
| 80×5 | 851 | 1360 | 1460 | 2250 |
| 80×10 | 1220 | 2000 | 2660 | 3460 |
| 100×5 | 1050 | 1650 | 1730 | 2660 |
| 100×10 | 1480 | 2390 | 3110 | 4020 |
| 120×10 | 1730 | 2750 | 3540 | 4560 |
| 160×10 | 2220 | 3470 | 4390 | 5610 |
| 200×10 | 2710 | 4180 | 5230 | 6660 |
Example: 50×10 mm bare copper busbar, 40 °C ambient
- Table value: for a single 50×10 mm bare copper bar per phase, I₀ = 852 A (35 °C ambient, 65 °C busbar).
- Correction: Δθ = 65 − 40 = 25 K (30 K under table conditions); with a busbar temperature of 65 °C the resistance correction stays 1, and the approximate relation gives the factor (25 / 30)^0.61 = 0.895.
- Result: I = 852 × 0.895 ≈ 762 A; cross-section 500 mm², current density 1.52 A/mm².
How many amps does a 30×10 copper busbar carry?
The DIN 43671 continuous current of a single 30×10 mm copper bar per phase is 573 A bare and 676 A painted (35 °C ambient, 65 °C busbar). An aluminum bar of the same size carries 445 A and 536 A respectively per DIN 43670. In an enclosed panel, the temperature rise is verified separately.
How many amps does a 40×10 copper busbar carry?
The DIN 43671 continuous current of a single 40×10 mm copper bar per phase is 715 A bare and 850 A painted (35 °C ambient, 65 °C busbar). An aluminum bar of the same size carries 557 A and 677 A respectively per DIN 43670. In an enclosed panel, the temperature rise is verified separately.
How many amps does a 60×10 copper busbar carry?
The DIN 43671 continuous current of a single 60×10 mm copper bar per phase is 985 A bare and 1,180 A painted (35 °C ambient, 65 °C busbar). An aluminum bar of the same size carries 774 A and 951 A respectively per DIN 43670. In an enclosed panel, the temperature rise is verified separately.
How many amps does a 80×10 copper busbar carry?
The DIN 43671 continuous current of a single 80×10 mm copper bar per phase is 1,240 A bare and 1,500 A painted (35 °C ambient, 65 °C busbar). An aluminum bar of the same size carries 983 A and 1,220 A respectively per DIN 43670. In an enclosed panel, the temperature rise is verified separately.
How is busbar capacity calculated?
The DIN table value is taken for the material, size, surface and number of parallel bars (35 °C ambient, 65 °C busbar) and corrected for the ambient and permitted busbar temperature.
What is checked in the final busbar selection?
Temperature rise in an enclosed panel must be verified according to IEC 61439. Busbar arrangement, spacing, connection points, short-circuit thermal withstand and electromechanical forces are checked separately.