Low Voltage Cables Selection Guide

Engineering guide to choosing NYA, NYAF, NYM, TTR, NYY, N2XH and aluminum NAYY/NA2XH low-voltage power cables by ampacity, insulation and fire performance.

What are low voltage cables? Low voltage cables are 300/500 V, 450/750 V, and 0.6/1 kV power and installation cables used for building wiring, switchgear panel interconnections, underground mains feeders, and industrial power distribution.

This guide explains how to select cables in the Low Voltage Cables category. For sizing calculations, use the Cable Ampacity Calculator and Voltage Drop Calculator.

Main low voltage cable groups

Cable comparison table

Cable TypeVoltage RatingConductor & InsulationJacket TypeTypical Application
NYA (H07V-U/R)450/750 VSolid/stranded Cu, PVCPVC or LSZHFixed conduit wiring for lighting and sockets
NYAF (H07V-K)450/750 VFlexible fine-stranded CuPVC or LSZHControl cabinet wire ducts and switchgear wiring
NYM / NHXMH300/500 VMulti-core CuPVC (NYM) / LSZH (NHXMH)Surface-mounted and damp-location fixed installations
TTR (H05VV-F)300/500 VFlexible multi-core CuPVC or LSZHPortable appliances, extension cords and light machinery
NYY0.6/1 kVCu, PVC insulation (70 °C)Black PVCDirect burial, outdoor trenches and cable ducts
N2XH0.6/1 kVCu, XLPE insulation (90 °C)Halogen-free (LSZH)Hospitals, malls, hotels and high-occupancy risers

Frequently asked questions

What is the difference between NYY and N2XH power cables?

Both are 0.6/1 kV distribution cables, but NYY uses PVC insulation (70 °C max conductor temperature) and a PVC sheath for outdoor/underground runs. N2XH uses cross-linked polyethylene (XLPE) insulation (90 °C operating temperature, giving higher current capacity for the same cross-section) and a low-smoke zero-halogen (LSZH) jacket required in public buildings.

Why is NYAF preferred over NYA inside electrical panels?

NYAF has a Class 5 fine-stranded flexible copper conductor that bends easily through tight panel wire ducts and terminates cleanly with cable ferrules, whereas NYA is rigid.

How should aluminum NAYY or NA2XH cables be terminated onto copper busbars?

Always use bimetal cable lugs (friction-welded aluminum barrel to copper palm) to prevent galvanic corrosion at the aluminum-to-copper joint.