N2XH FE180 (E90) Fire-Resistant Power Cables Selection Guide

When selecting N2XH FE180 (0.6/1 kV) fire-resistant power cables, compare mica-tape insulation integrity (FE180), E30/E60/E90 system continuity and differences vs N2XH.

This guide explains what to look for when choosing products in the N2XH FE180 Cables category for life-safety power circuits that must continue operating during an active fire, including fire pumps, smoke extraction fans, stairwell pressurization fans and emergency lighting.

Understanding FE180 (Insulation Integrity) and E30 / E60 / E90 (System Circuit Integrity)

Rated at 0.6/1 kV, N2XH FE180 (and NHXH FE180) cables wrap each copper conductor in a glass mica tape thermal barrier beneath XLPE/HFFR insulation and a low-smoke zero-halogen (LSZH) outer sheath:

Critical difference between standard N2XH and N2XH FE180

Standard N2XH cables are halogen-free and flame-retardant, but their insulation melts when engulfed in direct fire. Any life-safety load that must stay energized during building evacuation and firefighting requires N2XH FE180.

N2XH FE180 fire-resistant cable comparison table

Selection CriterionN2XH FE180 / E90 (Fire-Resistant Power)Standard N2XH (Halogen-Free Power)JE-H(St)H FE180 (Fire-Resistant Signal)
Voltage Rating0.6/1 kV life-safety power feeder0.6/1 kV general building power feeder300 V fire alarm & voice evacuation loop
Barrier ConstructionMica glass tape + XLPE/HFFR + LSZH jacketXLPE insulation + LSZH jacket (no mica barrier)Mica-taped twisted pairs + foil screen + orange LSZH
Operation in Fire180 min insulation integrity (FE180), E30/E60/E90Self-extinguishing & LSZH, but does not run in fireMaintains fire detection, siren & PA signaling in fire
Typical ApplicationFire pumps, smoke extraction/pressurization fans, emergency lightsNormal lighting, sockets, HVAC & general risersFire alarm control panels, detectors, call points & sounders

Frequently asked questions

Which building circuits require N2XH FE180 / E90 cables?

Fire protection regulations mandate circuit-integrity cables for fire booster pumps, smoke exhaust and stairwell pressurization fans, firefighter elevators, emergency escape lighting and fire alarm power supplies.

Can N2XH FE180 cables be fastened with plastic cable ties or nylon wall plugs?

No. To achieve E30/E60/E90 system circuit integrity, cables must be supported on fire-tested steel brackets, metal clips and steel anchors so the cable run does not collapse when exposed to fire temperatures.

What cross-sections are most common for N2XH FE180 circuits?

Emergency lighting and damper circuits use 3×1.5 mm² and 3×2.5 mm²; smoke extraction and pressurization fans use 4×2.5 mm² – 4×16 mm² or 5×2.5 mm² – 5×16 mm²; and main fire pump feeders use 4×25 mm² up to 3×240/120 mm².