Cam Switches Selection Guide

Cam switches are switches whose position is selected by turning the handle; on-off, step, reversing, star-delta and Dahlander types are chosen by the job.

This guide explains what to look at when choosing products in the Cam Switches category.

Cam switch types

How to read the product name

What to look at when choosing

  1. Contact diagram. When replacing a faulty switch, look not only at the name but at the number of positions, the handle angle and the terminal numbers of the old switch; on switches that do the same job, the terminal layout varies from manufacturer to manufacturer.
  2. Current and load type. The current in the product name is not valid for every load; for a switch that will directly switch a motor on and off, use the current or power value the manufacturer gives for motor loads.
  3. Number of poles. Chosen according to the number of conductors to be switched; in three-phase circuits where the neutral will also be cut, a three-phase + neutral or four-pole model is needed.
  4. Mounting. For a switch to be fitted to a panel door, the front frame size determines the layout; for a surface-mounted switch, the enclosure size does.

The difference between a cam switch and contactor control

A cam switch keeps its position mechanically. When power is cut and comes back, the motor fed by a switch left in the run position starts again. On machines where automatic restart is not wanted, control is built through a contactor or a motor protection circuit breaker with an undervoltage coil is used. With a star-delta cam switch, the operator determines the moment of changeover from star to delta; where the changeover must be time-based and automatic, a contactor star-delta starter is preferred; these products are listed in the Motor Control Equipment category. For transfer between the mains and a generator there is also the Transfer Switches category.

Brands in this category

Order notes

Cam switches are sold by the piece. Most of the products are lead-time items; the delivery time is confirmed before the order is placed. You can search for Metop and Opaş products by current and type name, and for Schneider Electric cam switches by manufacturer code such as K1B002ALH. If the enclosure is bought separately, the enclosure's current rating and switch type (on-off, reversing, star-delta) must be the same as the switch's.

Rotary cam switch comparison table

Cam Switch FunctionPoles / StepsTypical CurrentApplication ScenarioCategory Link
On-Off (0-1) cam switch1P – 6P16 A – 200 AMachine main isolation and door-interlocked panel switchingOn-Off Cam Switches
Changeover / reversing (1-0-2)1P – 6P16 A – 200 AManual mains-generator transfer and motor direction reversalChangeover Switches
Multi-step cam switch2 – 10 steps16 A – 125 AHeater stage selection, fan speed control, and tap switchingStep Cam Switches
Voltmeter / ammeter selector3-phase measurement10 A – 25 AMonitoring L1-L2-L3 phase voltages or currents on a single meterCommutator Switches

Frequently asked questions

How does a reversing cam switch work?

A reversing (forward-reverse) switch has a 0 position in the middle and one operating position on each side. On a three-phase motor, in one position it connects the phases directly, and in the other it swaps two phases; the motor then turns in the opposite direction. The motor is expected to stop before the direction is changed; applying reverse to a rotating motor is a heavy duty condition defined by a separate utilization category (AC-4). Separate reversing models are listed for single-phase motors.

Which should be chosen, a pole-changing switch with 0 or without 0?

In the model with 0 (1-0-2), there is an off position between the two positions in which the load is connected to neither circuit; the switch also serves as an on-off switch. In the model without 0, the load is always connected to one of the two circuits, and switching off is done with another switch. If the load needs to be left unpowered on site, the model with 0 is chosen. Verify from the manufacturer's contact diagram how the contacts behave during the changeover.

Can a star-delta cam switch be used with every motor?

No. The six winding ends of the motor must be brought out to the terminal box, and the motor must be suitable for delta-connected operation at the mains voltage; the voltage and connection information on the nameplate shows this. By turning the switch, the motor is connected first in star, then in delta, and the operator determines the moment of changeover. If the changeover is wanted to be timed and automatic, a contactor star-delta starter is used. Overload and short-circuit protection is installed separately.

Does the current written on a cam switch also apply to a motor?

Not always. IEC 60947-3, which covers cam switches, defines a switch's current together with the utilization category: AC-21 is for resistive loads, AC-22 for mixed resistive and inductive loads, and AC-23 for motors and highly inductive loads. The rated current of the same switch under a motor load is generally lower than under a resistive load. For a switch that will directly switch a motor on and off, use the current or motor power value the manufacturer gives for the AC-23 or AC-3 category.

Which motors is a Dahlander switch used with?

It is used with two-speed Dahlander motors, whose single winding can be connected for two different numbers of poles. In these motors the number of poles changes in a 1:2 ratio and the speed in a 2:1 ratio; in the constant-torque type the winding is connected in delta at low speed and in double star at high speed, and the motor has six connection terminals. The switch changes between these two connections with positions 0, 1 and 2. Two-speed motors with two separate windings require a different diagram; check the motor nameplate.