Current Transformer Ratio and VA Burden Calculator

Select the next standard current transformer ratio from line current and calculate total secondary VA burden including copper lead losses.

Formula used

R_loop = 2 × L × 0.0175 / S · P_wire = I_sn² × R_loop · S_total = S_meter + P_wire

Current transformer secondary cable loss and total VA burden table

Calculated for copper conductors (ρ = 0.0175 Ω·mm²/m, outgoing + return 2 × L) with a 1.5 VA meter/analyzer burden. Notice that a 1 A secondary reduces cable VA loss to 1/25 of a 5 A secondary.

One-way distance5 A · 2.5 mm² cable loss (VA)5 A · 2.5 mm² total burden (VA)5 A · 4 mm² cable loss (VA)1 A · 2.5 mm² cable loss (VA)
2 m0.702.200.440.03
5 m1.753.251.090.07
8 m2.804.301.750.11
10 m3.505.002.190.14
15 m5.256.753.280.21
20 m7.008.504.380.28
30 m10.5012.006.560.42

Example: 220 A line, 5 A secondary, 8 m of 2.5 mm² copper wire, 1.5 VA analyzer

  1. Next standard CT ratio: 250/5 A.
  2. Loop resistance (2 × 8 m): R = 0.1120 Ω; 5 A cable loss: P = 5² × R = 2.80 VA.
  3. Total burden: 1.5 + 2.80 = 4.30 VA → next standard CT rating: 5 VA.

How is current transformer (CT) VA burden calculated?

Total secondary burden is the sum of the connected instrument VA consumption and the secondary wire loss: S_total = S_device + I_s² × (2 × L × 0.0175 / S). The selected CT rated output (e.g. 5 VA, 10 VA, 15 VA) must be at least equal to S_total.

How is CT secondary wire VA loss calculated?

Multiply the round-trip copper loop resistance (R_loop = 2 × L × 0.0175 / S) by the square of the rated secondary current (5² = 25 or 1² = 1) and add the instrument VA burden.

When should a 1 A secondary CT be chosen over 5 A?

5 A CTs are standard inside a panel; when the distance between the CT and the analyzer or meter is long, a 1 A secondary cuts copper lead VA loss by a factor of 25.