Star-Delta and DOL Motor Current Calculator

Compare line current, winding branch current (IΔ = In / √3) and star contactor current (IY = In / 3) for direct-on-line (DOL) and star-delta motor starters.

Formula used

In = P / (√3 × U × cos φ × η) · IΔ = In / √3 · IY = In / 3

Direct-on-line (DOL) and star-delta current table · 400 V (cos φ 0.85, η 0.90, k = 6)

Formula results for cos φ 0.85, efficiency 0.90 and starting current ratio k = 6. In star-delta starting, the main and delta contactors carry the phase current (In / √3 ≈ 0.58 In) and the star contactor carries In / 3; actual selection uses the motor nameplate current and IEC 60947-4-1 AC-3 ratings.

Power (kW)Line current In (A)Main / delta contactor IΔ (A)Star contactor IY (A)DOL starting current (A)Star starting current (A)
1.52.831.630.9416.985.66
2.24.152.401.3824.918.30
35.663.271.8933.9611.32
47.554.362.5245.2815.09
5.510.385.993.4662.2620.75
7.514.158.174.7284.9028.30
1120.7511.986.92124.5341.51
1528.3016.349.43169.8156.60
18.534.9120.1511.64209.4369.81
2241.5123.9713.84249.0583.02
3056.6032.6818.87339.62113.21
3769.8140.3123.27418.86139.62
4584.9049.0228.30509.43169.81
55103.7759.9134.59622.63207.54
75141.5181.7047.17849.04283.01

Example: 15 kW, 400 V three-phase motor (cos φ 0.85, η 0.90, k = 6)

  1. Line current: In = 15,000 W / (√3 × 400 V × 0.85 × 0.90) = 28.30 A.
  2. Star-delta branch currents: main and delta contactors IΔ = In / √3 = 16.34 A; star contactor IY = In / 3 = 9.43 A.
  3. Starting current: 169.81 A in direct-on-line starting and 56.60 A in star starting.

How are contactor and thermal overload relay currents calculated in star-delta starting?

In a star-delta starter, the main contactor (KM) and delta contactor (KΔ) are connected in the winding loop and carry IΔ = In / √3 (about 58% of line current), while the star contactor (KY) carries IY = In / 3 (about 33% of line current). If the thermal overload relay is mounted under the main contactor in the phase loop, it is set to In / √3; if mounted on the supply line, it is set to In.

Why do branch currents differ in a star-delta starter?

When the main and delta contactors are wired in series with the motor windings, they carry 1/√3 of the line current (about 58%), while the star contactor carries 1/3 during starting.

How are the thermal relay and contactors verified?

Final selection must follow the motor nameplate current, AC-3 utilization category, starting time, transition delay and the manufacturer's type-1/type-2 coordination tables.