Contactor Latching (Start–Stop) Control Circuit: 13-14 NO / 21-22 NC Auxiliary Contacts and Coil Selection

Step-by-step contactor latching circuit with start–stop push buttons: A1-A2 coil, 13-14 NO holding contact, 21-22 NC interlock, 95-96 overload contact and coil voltage choice.

Contactor latching (a holding or seal-in circuit) keeps the coil energized through the contactor's own `13-14` normally open (NO) auxiliary contact after the momentary start button is released. Built with IEC 60947-4-1 contactors and IEC 60947-5-1 control devices, it is the basis of motor control and stops the motor restarting by itself when supply returns after an outage.

> Related Category: Browse models by current and coil voltage in Contactors, Auxiliary Contacts and Control Push Buttons.

1. What the terminal numbers mean

TerminalMeaning
A1 – A2Coil
1-2, 3-4, 5-6 (L1-T1, L2-T2, L3-T3)Main power poles
13-14Auxiliary contact in position 1, normally open (NO)
21-22Auxiliary contact in position 2, normally closed (NC)
33-34, 43-44NO contacts in positions 3 and 4
95-96Overload relay trip contact (NC)
97-98Overload relay signal contact (NO)

Rule: in a two-digit number the first digit is the position, the second the function. `1-2` is NC and `3-4` is NO, so `13-14` is the NO in position 1 and `21-22` the NC in position 2. Time-delayed contacts use `5-6` (NC) and `7-8` (NO).

2. Start–stop latching circuit step by step

The control circuit is a series chain:

Line (L) → control fuse → overload 95-96 → Stop button (NC) → Start button (NO) → coil A1; coil A2 → neutral (N)

For latching, the contactor's 13-14 contact goes in parallel with the start button:

  1. After the fuse, the control line enters overload terminal `95` and leaves `96` for the NC contact of the stop button.
  2. The stop output feeds both the NO contact of the start button and contactor terminal `13`.
  3. The start button output and contactor terminal `14` are joined and taken to coil terminal `A1`.
  4. Coil terminal `A2` goes to neutral (or the other side of the control transformer).

Operation: pressing start pulls the coil in, `13-14` closes and current keeps flowing through it after the button is released. Pressing stop or an overload trip on `95-96` breaks the chain, the coil drops out and `13-14` opens; the circuit waits for a new start.

3. The 21-22 NC contact: electrical interlock

In reversing and star-delta circuits two contactors closing together is a phase-to-phase short. To prevent it, the 21-22 NC contact of the other contactor is wired in series with each coil: while K1 is closed, K2 cannot be energized. Reversing duty adds a mechanical interlock as well. If the contactor lacks contacts, add front or side auxiliary contact blocks; to multiply control signals only, choose an auxiliary contactor.

4. Coil voltage selection

Coil voltageUseNote
24 V DCAutomation panels with PLC outputsFit a freewheeling diode or varistor suppressor
24 V ACMachine panels with a control transformerWet locations and touch risk
110 V ACExport machinery, transformer-fed control—
230 V ACLine-to-neutral control; most commonNeeds a neutral
400 V ACThree-phase panels without neutralControl taken between two phases

5. Button colours and safety (IEC 60204-1)

Frequently asked questions

Is the holding contact wired in series or parallel with the start button?

In parallel. The 13-14 NO contact bridges the start button, so coil current continues through it when the button is released.

Why is the stop button normally closed (NC)?

It sits in series with the coil and must open the circuit when pressed. NC wiring also fails safe: a broken wire or loose terminal stops the machine.

What is the difference between 13-14 and 21-22 contacts?

13-14 is a normally open (NO) contact used for latching and signalling. 21-22 is a normally closed (NC) contact used for electrical interlocking between two contactors.

The contactor pulls in on start but drops out on release. Why?

The holding path is not working: 13-14 is not in parallel with the start button, an NC contact was used by mistake, or the auxiliary contact is faulty.

AC or DC contactor coil?

Use 24 V DC in panels with a PLC and 24 V supply, and 230 V AC in classic line-to-neutral control. A DC coil is silent and less sensitive to voltage dips.