DIN Rail Terminal Block, DIN 46228 Ferrule Color Codes, and Cable Lug Sizing Guide

IEC 60947-7-1 DIN rail terminal block current ratings, DIN 46228-4 bootlace ferrule color codes, twin ferrules, and DIN 46235 vs standard tubular copper cable lug sizing.

Matching terminal blocks, bootlace ferrules, and tubular cable lugs eliminates loose-clamp hot spots and arc failures inside industrial control and distribution panels. Clamping bare Class 5 fine-stranded wire (H05V-K / H07V-K) directly under a screw shears strands and raises contact resistance; compliant panel builds use DIN 46228-4 insulated ferrules on control wires, DIN 46235 / tubular lugs on power feeders, and IEC 60947-7-1 terminal blocks on 35 mm DIN rails.

> Related Category: Filter termination components in Terminal Blocks, DIN Rail Terminal Blocks, Cable Ferrules, and Cable Lugs.

IEC 60947-7-1 DIN rail terminal block current and torque ratings

Rated cross-sectionIEC 60947-7-1 test currentTypical screw torqueTypical panel circuit
2.5 mm²24 A0.4 – 0.6 NmPLC I/O, sensors, control & 16 A final circuits
4 mm²32 A0.5 – 0.8 NmMotor control & 20–25 A feeders
6 mm²41 A0.8 – 1.2 Nm32 A power branches & sub-circuits
10 mm²57 A1.2 – 1.8 NmPFC capacitor stages & 40–50 A feeders
16 mm²76 A2.0 – 2.5 NmSub-panel incomers & 63 A breaker outputs
35 mm²125 A3.2 – 4.0 NmMain distribution & heavy motor feeders
70 – 240 mm²192 – 415 A6.0 – 20 Nm (hex / stud)Main busbar incoming feeders

Compare clamping technologies in Screw vs Spring and Push-in Terminal Block Difference, and use 450 V lever or push-wire junction box terminal blocks inside wall boxes.

DIN 46228-4 insulated bootlace ferrule color code chart

Tinned electrolytic copper cable ferrules identify conductor size by plastic collar color (note the difference between German DIN 46228-4 Series 2 and French Series 1 on 0.75, 2.5, and 4 mm²):

Conductor sizeDIN 46228-4 collar colorFrench (Series 1) colorStandard barrel length
0.50 mm²WhiteWhite8 mm
0.75 mm²GreyBlue8 mm
1.0 mm²RedRed8 mm
1.5 mm²BlackBlack8 or 10 mm
2.5 mm²BlueGrey8 or 12 mm
4.0 mm²GreyOrange10 or 12 mm
6.0 mm²YellowGreen12 mm
10 mm²RedBrown12 or 18 mm
16 mm²BlueWhite / Ivory12 or 18 mm

Always crimp using a ratcheting ferrule crimping plier rather than side-cutters, and use twin (dual-entry) ferrules whenever bridging two fine-stranded wires into one terminal cage.

DIN 46235 vs standard tubular copper cable lugs

Tubular copper lug part numbers state conductor cross-section (`mm²`) – stud bolt size (`M`) (for example, 35–8 fits a 35 mm² copper conductor onto an M8 stud with an Ø8.4 mm palm hole):

Never crimp bare aluminum conductors into pure copper lugs—see Aluminum (NAYY) vs Copper (NYY) Cable Sizing and Bimetallic Termination.

Frequently asked questions

Should ferrules be crimped onto solid Class 1 wire?

No. Class 1 solid conductors (NYA, NYM) clamp directly into screw and push-in terminals; ferrules are engineered specifically for Class 5/6 fine-stranded flexible conductors.

Can tinned solder replace a ferrule on stranded wire?

Never (IEC 60999-1 / IEC 60364-5-52). Solder creeps under screw pressure and thermal cycling, loosening the joint until arcing and overheating occur.

Can bare stranded wire enter a push-in terminal block without a ferrule?

Yes, provided you depress the orange actuator pusher button with a screwdriver to open the spring; direct tool-free push-in insertion requires either a solid conductor or a gas-tight crimped ferrule.

Why does stud hole size matter on a 50 mm² lug (e.g., 50-8 vs 50-12)?

Mounting an oversized M12 palm hole onto an M8 busbar bolt drastically shrinks palm contact area and allows the lug to twist, causing localized busbar heating.