VFD Parameters, V/f vs Vector Control and Braking Resistor Sizing

Commissioning parameters of an AC variable frequency drive, V/f vs vector control, drive current selection and braking resistor ohm and watt sizing.

An AC variable frequency drive (VFD, frequency inverter) sets induction motor speed by changing supply frequency: `n = 120 × f / number of poles`. With drives built to the IEC 61800 series, good results depend on entering the motor nameplate data, picking the right control mode and, where needed, sizing the braking resistor correctly.

> Related Category: Browse models by rating and input voltage in Variable Frequency Drives, AC Motor Drives and Braking Resistors.

1. Drive selection: current, not just kW

2. Parameters entered at first start-up

Parameter numbers differ by brand; the content is the same:

ParameterWhat to enterIf wrong
Motor rated voltage, current, frequency, speed, cos φFrom the nameplateOverheating, low torque, false overload alarms
Motor thermal (overload) currentNameplate currentUnprotected motor or nuisance trips
Acceleration / deceleration ramp3–30 s depending on inertiaShort ramp: overcurrent or DC bus overvoltage fault
Minimum / maximum frequencye.g. 20–50 HzPump runs dry, fan overspeeds
Command and reference sourceKeypad, terminals, fieldbusDrive will not start
Carrier (switching) frequency2–16 kHzHigh value: quiet motor, more heat and leakage current
Motor identification (autotune)Mandatory in vector modeWeak torque at low speed

Above 50 Hz the output voltage cannot rise further, so the motor enters field weakening and torque falls inversely with frequency.

3. V/f control vs vector control

Control modePrincipleLow-speed torqueSuitable load
V/f (scalar)Constant voltage/frequency ratio (400 V / 50 Hz = 8 V/Hz)Weak below 3–5 HzFans, pumps, several motors on one drive
Sensorless vector (SVC)Motor model separates flux and torque currentUp to 150% at 0.5–1 HzConveyors, mixers, extruders, compressors
Closed-loop vectorEncoder feedbackFull torque at zero speedHoists, lifts, winders, precise speed

A quadratic V/f curve saves energy on fans and centrifugal pumps. When one drive feeds several motors, use V/f only and give each motor its own thermal overload protection.

4. Braking resistor sizing

A motor decelerating a load quickly acts as a generator and pumps energy into the DC bus. When bus voltage passes a threshold the brake chopper switches the resistor in. The chopper threshold is typically 750–800 V DC on 400 V class drives and about 380–400 V DC on 230 V class.

  1. Ohmic value: never go below the minimum resistance in the drive manual; too low a value destroys the chopper transistor. Peak braking power is `P = U² / R`: `780² / 100 Ω ≈ 6.1 kW`.
  2. Continuous power (W): `P continuous = P braking × duty cycle (ED)`. Example: 3 kW of braking for 6 s in a 60 s cycle → ED = 10% → `3,000 × 0.10 = 300 W`. Choose 400–500 W for thermal margin.
  3. Load type: hoist lowering and long braking push ED to 40–100%, so resistor power approaches motor power.

Connect the resistor to the `B+ / BR` (or `P / PB`) terminals with a short screened cable. Its surface can exceed 200 °C, so mount it in free air away from flammable material. Simply lengthening the deceleration ramp removes the need for a resistor in most fan and pump applications.

5. Wiring and protection

Frequently asked questions

Can a three-phase motor run from a single-phase 230 V supply?

Yes. A 230 V single-phase input drive outputs 3 × 230 V; a 230/400 V motor connected in delta delivers full power. In practice this is used up to about 2.2–3 kW.

Should I use V/f or vector control?

V/f is enough for fans and pumps. Conveyors, mixers and lifting applications that need high torque at low speed call for vector control with motor identification completed.

When is a braking resistor needed?

When a high-inertia load must stop quickly or the load drives the motor (hoist lowering, inclined conveyors). A DC bus overvoltage fault during deceleration is the typical sign.

What happens if the braking resistor value is too low?

Chopper current exceeds its limit and the brake transistor fails. The resistor must be equal to or higher than the minimum ohmic value in the manual.

Can a motor run above 50 Hz on a drive?

Yes, up to its mechanical speed limit, but torque falls above 50 Hz. Check the motor maker's maximum speed for bearing and fan limits.