What Is a PDU? Rack PDU Types, C13–C19 Outlets and Rack Power Sizing

What a PDU (power distribution unit) is and how it differs from a power strip; basic, metered and switched PDUs, C13–C14 and C19–C20 connectors and 16 A / 32 A rack power sizing.

A PDU (power distribution unit) is a multi-outlet unit mounted in a 19-inch rack that distributes one supply line to servers and network equipment. It differs from a household power strip in its rack mounting, continuous full-load design, IEC C13–C19 outlets and, depending on model, current metering and remote switching.

> Related Category: Browse models by outlet type and current in PDU Power Distribution Units, and UPS Uninterruptible Power Supplies for the supply side.

1. PDU types

TypeFeatureUse
Basic PDUDistributes power only; may have a breaker or switchSmall network racks, office comms rooms
Metered PDULocal display shows total current (A)Load balancing, overload watch
Monitored PDUCurrent, voltage and energy read over the networkData centres, energy reporting
Switched PDUEach outlet switched remotelyRemote sites, rebooting a hung device
PDU with ATSTransfers automatically between two sourcesDual feed for single-supply devices

By mounting: a horizontal (1U–2U) PDU fits the rack rails with 6–12 outlets; a vertical (0U) PDU sits in the rear side space, uses no rack units and offers up to 20–40 outlets.

2. Input and output connectors

ConnectorRated currentWhere used
Earthed household socket16 AModems, adapters, office devices
IEC C13 outlet / C14 plug10 AServers, switches, storage; the most common outlet
IEC C19 outlet / C20 plug16 AHigh-power servers, blade chassis, large UPS units
CEE (IEC 60309) plug, single-phase 16 A / 32 A16 A / 32 APDU input lead, latching connection
CEE plug, three-phase 16 A / 32 A3 × 16 A / 3 × 32 AHigh-density racks

3. Rack power sizing

The power a PDU can carry is limited by input current and voltage:

PDU inputMaximum powerRecommended continuous load (80%)
Single-phase 16 A, 230 V3.7 kW≈ 2.9 kW
Single-phase 32 A, 230 V7.4 kW≈ 5.9 kW
Three-phase 16 A, 400 V11 kW≈ 8.8 kW
Three-phase 32 A, 400 V22 kW≈ 17.7 kW

Steps:

  1. Add measured or manufacturer-stated typical consumption, not nameplate ratings; a power supply label is often twice real consumption.
  2. Compare the total with the 80% limit of the PDU.
  3. Leave room to grow; provide at least 20% more outlets than devices.

Example: 8 servers × 350 W + 2 switches × 150 W = 3,100 W. That exceeds the 80% limit of one 16 A PDU (2.9 kW); use a 32 A PDU or two separate 16 A lines.

4. A+B dual feeds

For dual-supply devices fit two PDUs per rack: feed A from one UPS and feed B from a second UPS or a separate line. One power supply of each device goes to A, the other to B.

Rule: in normal operation each PDU should stay below 40% of its rating. If one feed fails the whole load moves to the other and remains under 80%. With both PDUs at 70%, the surviving feed trips and the whole rack goes down.

For UPS sizing see Online vs Line-Interactive UPS, kVA to kW and Battery Runtime.

5. Selection notes

Frequently asked questions

What does PDU mean and what does it do?

Power distribution unit. It distributes the single supply entering a rack to servers, switches and other devices; advanced models meter consumption and switch outlets remotely.

What is the difference between a PDU and a power strip?

A PDU mounts in a 19-inch rack, is built for continuous full load and offers IEC C13–C19 outlets. A power strip is for home and office use with no rack mounting or metering.

What is the difference between C13 and C19?

A C13 outlet carries 10 A and a C19 outlet 16 A, and the plug shapes differ. Standard servers and switches use C13; high-power servers and blade chassis use C19.

How many servers fit on a 16 A PDU?

The continuous limit is about 2.9 kW. At 350 W typical per server, 8 servers sit at the limit; 6–7 is safe.

What is the difference between a metered and a switched PDU?

A metered PDU only shows current. A switched PDU also turns each outlet on and off over the network, so a remote device can be rebooted without a site visit.