Cable Trunking and Conduit Fill Calculator

Find the total external cross-sectional area of your cables from outer diameter and count, and see the required internal area and standard trunking size.

Formula used

A₁ = π × d² / 4 · A_total = N × A₁ · A_pathway = A_total / k_fill

Standard cable trunking cross-sectional area and usable fill table

Nominal internal cross-section (W × H) and usable cable area at 40% and 50% maximum fill ratios. Leave reserve space for heat dissipation, bending radius and future cable additions.

Trunking size (mm)Total area (mm²)Usable area at 40% (mm²)Usable area at 50% (mm²)
25×16400160200
40×16640256320
40×251000400500
40×401600640800
60×4024009601200
80×40320012801600
60×60360014401800
100×40400016002000
80×60480019202400
100×60600024003000
120×60720028803600

Example: 8 cables with 12 mm outer diameter at 50% trunking fill

  1. Single cable area: A₁ = π × 12² / 4 = 113.10 mm².
  2. Total cable area for 8 cables: A = 8 × 113.10 = 904.78 mm².
  3. Required trunking area at 50% fill: 1809.56 mm²; first standard trunking size: 60×40 mm.

What should the cable trunking and conduit fill ratio be?

In conduits and pipes, a maximum fill factor of around 40% is commonly used to prevent jamming and jacket damage during pulling. In cable trunking and panel ducts, 50% fill leaves room for air circulation and future spare circuits.

Why is overall outer diameter used for trunking fill?

Nominal mm² only measures the metallic core; insulation and outer sheath make the physical cable much wider, so space occupancy is calculated from outer diameter d via A = π × d² / 4.

Why are conduit and trunking fill ratios limited to 40%–50%?

Limiting conduit fill to 40% and trunking fill to 50% prevents jacket damage during pulling, accounts for air voids between round cables and preserves heat dissipation.