What Is a Phase Sequence Relay? Types and Selection Criteria

A phase sequence relay is a monitoring relay that watches the order of the phases in a three-phase supply and opens its contact when the order is reversed, preventing reverse motor rotation.

Original Welibaba illustration of Phase Sequence Protection Relays

A phase sequence relay (phase sequence protection relay) is a monitoring relay that watches the L1-L2-L3 order of the phases in a three-phase supply and, when the order is reversed, opens its output contact so that the motor contactor cannot pull in. It is used on pump, compressor, fan, conveyor, lift and crane motors where reverse rotation causes damage, and in construction site and generator panels whose connection changes often. The relay does not interrupt the motor current itself; its contact is wired into the contactor coil circuit.

Types

Catalog models

ModelMonitoringMeasuring voltageOutput
Entes FR-02Phase sequence220–230 V AC, three phases + neutral connectedNot specified
Siemens 3UG5511-1AR20Phase sequence3×160–690 V AC1 changeover contact
Siemens 3UG5511-1BR20Phase sequence3×160–690 V AC2 changeover contacts, automatic reset
Siemens 3UG5512-1AR20Phase sequence, phase failure, 10% asymmetry3×160–690 V AC1 changeover contact, automatic reset
Siemens 3UG5514-1BR20Phase sequence, phase failure, asymmetry, undervoltage3×160–690 V AC, 15–70 Hz2 changeover contacts
Siemens 3UG5616-1CR20Digital-setting line monitoringNot specified2 changeover contacts, automatic or manual reset
Siemens 3UG5618-1CR20Digital-setting line monitoring3×90–690 V AC2 changeover contacts

Values are taken from the product names and Siemens product data. The Siemens 3UG5501-1AW30 (0.5–500 kΩ sensitivity) and 3UG5642-1CW30 in this category are not phase sequence relays but relays with other monitoring functions.

Selection criteria

  1. Faults to monitor: If only the direction of rotation matters, a phase sequence relay is enough. To also stop the motor running on two phases, choose a model that monitors phase failure, and on an unbalanced supply asymmetry as well.
  2. Measuring voltage: The relay's voltage range must cover your supply. The Entes FR-02 is for a connection with neutral at 220–230 V AC; the Siemens 3UG55 models cover wide ranges such as 3×160–690 V AC.
  3. Neutral connection: If the panel has no neutral conductor, choose a model that does not need a neutral connection.
  4. Output contact: One changeover contact is enough to drive the contactor coil. If you also need a fault alarm or a signal to a PLC, choose a model with two changeover contacts.
  5. Reset: On machines where an unexpected restart is dangerous, prefer a model with selectable manual reset instead of automatic reset.

Common mistakes

Brands in the catalog

The Phase Sequence Protection Relays category has 9 active products: Siemens 8, Entes 1. Relays that monitor phase failure, asymmetry and voltage limits together are in Phase and Motor Protection Relays, and relays that monitor voltage only are in Voltage Protection Relays. When a generator or site connection is renewed, measure the order before the first start with Phase Sequence Testers.

Frequently asked questions

What does a phase sequence relay do?

It stops a three-phase motor from running in the wrong direction. If the phases are not in L1-L2-L3 order, the relay keeps its contact open and the contactor does not pull in; the motor does not start.

What is the difference between a phase sequence relay and a phase protection relay?

A phase sequence relay monitors only the order, and some models also phase failure. A phase protection relay also monitors phase failure, asymmetry and over- or undervoltage. Choose a phase sequence relay when only the direction of rotation matters, and a phase protection relay for motor protection.

How is a phase sequence fault corrected?

Swap any two phases on the supply side; this also reverses the motor's direction of rotation.

Does a phase sequence relay trip when a phase is lost?

It depends on the model. A relay that monitors only the phase sequence may not detect phase loss. The Siemens 3UG5512-1AR20 and 3UG5514-1BR20 also monitor phase failure.