LV Surge Arrester (SPD) Selection: Type 1, Type 2 and Type 3 Wiring and Cable Sizing

Type 1, Type 2 and Type 3 SPDs per IEC 61643-11, reading Uc, Up, In and Iimp, 3+1 and 4+0 connections in TT and TN boards and the 0.5 m lead length rule.

A low-voltage surge arrester (SPD, surge protective device) diverts lightning and switching overvoltages to earth within microseconds and so protects equipment in the panel. IEC 61643-11 sorts SPDs by test class into Type 1, Type 2 and Type 3 (formerly classes B, C, D); protection only works when each stage sits in the right board with short connections.

> Related Category: Browse models by class and pole configuration in Low Voltage Surge Arresters.

1. Type 1 vs Type 2 vs Type 3

ClassFormer nameTest waveformTypical ratingLocation
Type 1B10/350 µs lightning impulse current (`Iimp`)12.5–25 kA per poleMain distribution board; buildings with external lightning protection or overhead supply
Type 2C8/20 µs (`In`, `Imax`)In 20 kA, Imax 40 kAMain board (no lightning protection system) and every sub-board
Type 3DCombination wave (1.2/50 µs voltage + 8/20 µs current)Uoc 6–10 kVDirectly ahead of sensitive equipment, socket or machine panel

At the same peak, a 10/350 µs impulse carries roughly 20 times the energy of an 8/20 µs impulse, so only Type 1 can handle partial direct lightning current. Combined Type 1 + 2 devices merge both stages in one body for the main board.

2. Reading the nameplate

3. Connection scheme by system type

SystemThree-phaseSingle-phaseNote
TN-S4+0: four varistors from L1, L2, L3, N to PE2+0Most common board type
TT3+1: three varistors L1, L2, L3 to N plus a spark gap N to PE1+1May be installed upstream of the RCD; no leakage to earth as varistors age
TN-C3+0: L1, L2, L3 to PEN1+0No neutral pole

A 4+0 scheme is not used in TT systems because an end-of-life varistor could put a dangerous voltage on PE. To identify the system type see Earth Rod Selection and TT / TN Systems.

4. Lead length and conductor sizes

The 0.5 m rule: the total length of the conductors from the line busbar to the SPD and from the SPD to the earth bar must not exceed 0.5 m. Under surge current each metre of conductor adds roughly 1 kV; one extra metre lifts a 1.5 kV Up above 2.5 kV at the equipment. If the length cannot be shortened, use a V connection where incoming and outgoing conductors meet directly on the SPD terminal.

Conductor (IEC 60364-5-53, clause 534)Type 1Type 2
Line and neutral connecting conductorMin. 6 mm² copperMin. 2.5 mm² copper
Earth (PE) connecting conductorMin. 16 mm² copperMin. 6 mm² copper

5. Status indicator and replacement

In varistor SPDs a thermal disconnector isolates the element at end of life and the window turns from green to red. Pluggable types need only a new module. Models with a remote contact report the fault to a pilot lamp or automation system. Remove SPD modules before insulation resistance testing; otherwise the test voltage makes the varistor conduct and the reading is wrong.

Frequently asked questions

What do class B, C and D arresters mean?

They are the former German classes: B = Type 1 (lightning current, 10/350 µs), C = Type 2 (8/20 µs, distribution board), D = Type 3 (fine protection near equipment). B+C means a combined Type 1 + 2 device.

Which SPD is used in a home?

A dwelling without a lightning protection system and fed by underground cable needs a Type 2 (In 20 kA, Imax 40 kA) in the board after the meter. With a lightning protection system or overhead service, fit Type 1 + 2 in the main board.

Is the SPD installed before or after the RCD?

Preferably before. Surge current through an RCD can trip or damage it. In TT systems an upstream SPD must be a 3+1 (1+1 for single-phase) design.

What size should the SPD earth conductor be?

At least 16 mm² copper for Type 1 and 6 mm² for Type 2, taking the shortest, straightest route to the earth bar.

What if the SPD indicator turns red?

The protective element is disconnected; the installation keeps running but without surge protection. Replace the module or device with the same Uc and class.