Kraus & Naimer CA10 A202 DÖKME On-Off Cam Switch, 3-Pole, 20 A, Bulk Version
- Brand: Kraus & Naimer
- SKU: CA10 A202 DÖKME
- MPN: CA10 A202 DÖKME
- Price: 996.00 TRY + VAT · incl. VAT 1195.20 TRY
- Availability: Made to order
- On-Off Switches
- Kraus & Naimer On-Off Switches
- Selection guide: On-Off Cam Switches (0-1) Selection Guide
Kraus & Naimer CA10 A202 DÖKME is the bulk version of a 3-pole, 20 An on-off cam switch. The switch has positions 0-1, a switching angle of 60° and 2 levels. Size type S0. Rated insulation voltage is 690 V (AC 50/60 Hz and DC) and rated impulse withstand voltage is 6 kV (switch), 4 kV (switch disconnector). AC-21A rated operational current is 20 A over 20–690 V; three-phase AC-3 rated power (380–440 V) is 5.5 kW; AC-23A rated power (380–440 V) is 7.5 kW. Maximum fuse rating gG 25 A; rated short-time withstand current 140 A (1 s); power loss per pole 0.9 W. The terminals accept stranded conductors up to 2 x 2.5 mm²; tightening torque is 0.6 Nm (5 lb-in); operating temperature is -25…+60 °C. It is used to switch a circuit on and off manually.
| Size Type | S0 |
|---|---|
| Number of Poles | 3P |
| Series | CA10 |
| Function Code | A202 |
| Switch Function | Aç-Kapa (0-1) |
| Switch Positions | 0-1 |
| Number of Positions | 2 |
| Switching Angle | 60° ° |
| Number of Levels | 2 |
| Rated Current | 20 A |
| Conventional Free Air Thermal Current (Ith) | 20 A |
| Ambient temperature for rated current | 55 °C (24 hours, tepe 60 °C) |
| Conventional Enclosed Thermal Current (Ithe) | 20 A |
| Rated Insulation Voltage (Ui) | 690 V (AC 50/60 Hz and DC) |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV (circuit breaker); 4 kV (switch-disconnector) |
| Overvoltage category | III |
| Pollution Degree | 3 |
| Rated Operational Current AC-15 (Ie) | 220–240 V: 6 A; 380–440 V: 4 A |
| Rated Operational Current AC-20A (Ie) | 690 V: 20 A |
| Rated Operational Current AC-21A (Ie) | 20–690 V: 20 A |
| Rated Operational Current AC-22A (Ie) | 220–500 V: 20 A; 660–690 V: 20 A |
| Rated Operational Power AC-2 (Pe) | 3-phase: 220–240 V 4 kW; 380–440 V 7.5 kW; 500 V 10 kW; 660–690 V 10 kW |
| Rated Operational Power AC-3 (Pe) | 3-phase: 220–240 V 3 kW; 380–440 V 5.5 kW; 500 V 5.5 kW; 660–690 V 5.5 kW. 1-phase: 110–120 V 0.6 kW; 220–240 V 2.2 kW; 380–440 V 3 kW |
| Rated Operational Power AC-4 (Pe) | 3-phase: 220–240 V 0.55 kW; 380–440 V 1.5 kW; 500 V 1.5 kW; 660–690 V 1.5 kW. 1-phase: 110–120 V 0.3 kW; 220–240 V 0.75 kW; 380–440 V 1.5 kW |
| Rated Operational Power AC-23A (Pe) | 3-phase: 220–240 V 3.7 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 110–120 V 0.75 kW; 220–240 V 2.5 kW; 380–440 V 3.7 kW |
| Maximum Fuse Current | gG 25 A |
| Rated Short-Time Withstand Current (Icw) | 140 A (1 s) |
| Breaking Capacity | 220–240 V: 150 A; 380–440 V: 150 A; 660–690 V: 80 A |
| Power Loss per Pole | 0.9 W |
| Solid Conductor Cable Cross-Section | 0.5–2.5 mm2 |
| Stranded Conductor Cable Cross-Section | 2x2.5 mm2 |
| Flexible Conductor Cross-Section | 0.75–2.5 mm2 |
| Conductor Cross-Section with Ferrule | 0.5–2.5 mm2 |
| Cable section (AWG/MCM) | AWG 14 (flexible); AWG 12 (solid or stranded) |
| Conductor Material | Copper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered) |
| Tightening Torque | 0.6 Nm (5 lb-in) |
| Recommended Screw Driver | Pozidriv/Phillips PH1; slotted 0.8 x 4 mm (DIN 5264) |
| Contact Type | Rigid bridging link |
| Contact Material | Silver |
| Connection Type | Screw terminal |
Shipping & assurance