Kraus & Naimer CA10 A221 DÖKME Changeover Cam Switch without OFF, 2-Pole, 20 A, Bulk Version
- Brand: Kraus & Naimer
- SKU: CA10 A221 DÖKME
- MPN: CA10 A221 DÖKME
- Price: 1195.00 TRY + VAT · incl. VAT 1434.00 TRY
- Availability: Made to order
- Pole-Changing Reversing Switches
- Kraus & Naimer Pole-Changing Reversing Switches
- Selection guide: Pole-Changing and Reversing Cam Switches Selection Guide
Kraus & Naimer CA10 A221 DÖKME is the bulk version of a 2-pole, 20 A changeover cam switch without an OFF position. The switch has positions 1-2, a switching angle of 60° and 2 levels. Size type S0. Rated insulation voltage is 690 V (AC 50/60 Hz) and rated impulse withstand voltage is 6 kV (switch), 4 kV (switch disconnector). AC-21A rated operational current is 20 A over 20–690 V; single-phase AC-3 rated power (220–240 V) is 2.2 kW; AC-23A rated power (220–240 V) is 2.5 kW. Maximum fuse rating gG 25 A; rated short-time withstand current 140 A (1 s); power loss per pole 0.9 W. The terminals accept stranded conductors up to 2 x 2.5 mm²; tightening torque is 0.6 Nm (5 lb-in); operating temperature is -25…+60 °C. It is used to transfer a load directly between two circuits or sources; there is no OFF (0) position.
| Size Type | S0 |
|---|---|
| Number of Poles | 2P |
| Series | CA10 |
| Function Code | A221 |
| Switch Function | Sıfırsız Enversör (1-2) |
| Switch Positions | 1-2 |
| Number of Positions | 2 |
| Switching Angle | 60° ° |
| Number of Levels | 2 |
| Rated Current | 20 A |
| Conventional Free Air Thermal Current (Ith) | 20 A |
| Ambient temperature for rated current | 55 °C (24 hours, tepe 60 °C) |
| Conventional Enclosed Thermal Current (Ithe) | 20 A |
| Rated Insulation Voltage (Ui) | 690 V (AC 50/60 Hz) |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV (circuit breaker); 4 kV (switch-disconnector) |
| Overvoltage category | III |
| Pollution Degree | 3 |
| Rated Operational Current AC-15 (Ie) | 220–240 V: 6 A; 380–440 V: 4 A |
| Rated Operational Current AC-20A (Ie) | 690 V: 20 A |
| Rated Operational Current AC-21A (Ie) | 20–690 V: 20 A |
| Rated Operational Current AC-22A (Ie) | 220–500 V: 20 A; 660–690 V: 20 A |
| Rated Operational Power AC-2 (Pe) | 3-phase: 220–240 V 4 kW; 380–440 V 7.5 kW; 500 V 10 kW; 660–690 V 10 kW |
| Rated Operational Power AC-3 (Pe) | 3-phase: 220–240 V 3 kW; 380–440 V 5.5 kW; 500 V 5.5 kW; 660–690 V 5.5 kW. 1-phase: 110–120 V 0.6 kW; 220–240 V 2.2 kW; 380–440 V 3 kW |
| Rated Operational Power AC-4 (Pe) | 3-phase: 220–240 V 0.55 kW; 380–440 V 1.5 kW; 500 V 1.5 kW; 660–690 V 1.5 kW. 1-phase: 110–120 V 0.3 kW; 220–240 V 0.75 kW; 380–440 V 1.5 kW |
| Rated Operational Power AC-23A (Pe) | 3-phase: 220–240 V 3.7 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 110–120 V 0.75 kW; 220–240 V 2.5 kW; 380–440 V 3.7 kW |
| Maximum Fuse Current | gG 25 A |
| Rated Short-Time Withstand Current (Icw) | 140 A (1 s) |
| Breaking Capacity | 220–240 V: 150 A; 380–440 V: 150 A; 660–690 V: 80 A |
| Power Loss per Pole | 0.9 W |
| Solid Conductor Cable Cross-Section | 0.5–2.5 mm2 |
| Stranded Conductor Cable Cross-Section | 2x2.5 mm2 |
| Flexible Conductor Cross-Section | 0.75–2.5 mm2 |
| Conductor Cross-Section with Ferrule | 0.5–2.5 mm2 |
| Cable section (AWG/MCM) | AWG 14 (flexible); AWG 12 (solid or stranded) |
| Conductor Material | Copper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered) |
| Tightening Torque | 0.6 Nm (5 lb-in) |
| Recommended Screw Driver | Pozidriv/Phillips PH1; slotted 0.8 x 4 mm (DIN 5264) |
| Contact Type | Rigid bridging link |
| Contact Material | Silver |
| Connection Type | Screw terminal |
Shipping & assurance
For made-to-order products, the procurement and carrier hand-over time is shared with the quotation.
In rare cases, all or part of an order may be unavailable due to stock or procurement updates. In this case, the customer is informed and the relevant product is cancelled and refunded. A product being open for sale does not guarantee that it is in physical store stock.