Kraus & Naimer KG105 T203/75 KL71 Emergency Stop Main Switch, 3-Pole, 125 A, in Enclosure (KL71)
- Brand: Kraus & Naimer
- SKU: KG105 T203/75 KL71
- MPN: KG105 T203/75 KL71
- Price: 16017.66 TRY + VAT · incl. VAT 19221.19 TRY
- Availability: Made to order
- Load Break Switches
- Kraus & Naimer Load Break Switches
- Selection guide: What Is a Load Break Switch? Types and Selection Criteria
Kraus & Naimer KG105 T203/75 KL71 is a 125 A (Ith), 3-pole emergency stop main switch (red handle, yellow front plate); supplied as a maintenance and safety switch in a KL series plastic enclosure (KL71), IP66/67, enclosure size 250 x 145 x 107 mm. Ratings: rated insulation voltage Ui 690 V, impulse withstand voltage Uimp 6 kV, AC-21A 125 A, three-phase motor rating at 380–440 V: AC-3 37 kW, AC-23A 45 kW, maximum fuse 125 A gG, short-time withstand current 2000 A (1 s). Connection: flexible conductors 4–35 mm², solid or stranded conductors 2.5–50 mm², terminal tightening torque 3 Nm. The enclosure has IP66/67 protection and is flame resistant to UL94 V-0; a ground terminal and a safety interlocked cover are standard equipment. The KG and C316 series switches exceed the requirements of IEC 60947-3 / EN 60947-3 (VDE 0660 part 107), IEC/EN 60204 and VDE 0113 and are used as switch disconnectors, main switches and maintenance switches.
| Number of Poles | 3P |
|---|---|
| Rated Current | 125 A |
| Mounting Type | KL71 ile kutulu (bakım and emniyet şalteri) |
| IP Rating | IP66/67 |
| Series | KG105 |
| Size Type | S1 |
| Function Code | T203 |
| Switch Function | Acil Durdurma Fonksiyonlu Ana Şalter (0-1) |
| Switch Positions | 0-1 |
| Number of Positions | 2 |
| Handle Color | Red (sarı ön plaka) |
| Conventional Free Air Thermal Current (Ith) | 125 A |
| Ambient temperature for rated current | 50 °C (24 hours, tepe 55 °C) |
| Conventional Enclosed Thermal Current (Ithe) | 125 A |
| Rated Insulation Voltage (Ui) | 690 V (AC 50/60 Hz) |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Overvoltage category | III |
| Pollution Degree | 3 |
| Rated Operational Current AC-20A (Ie) | 690 V: 125 A |
| Rated Operational Current AC-21A (Ie) | 20–690 V: 125 A |
| Rated Operational Current AC-22A (Ie) | 220–500 V: 125 A; 660–690 V: 90 A |
| Rated Operational Power AC-3 (Pe) | 3-phase: 220–240 V 22 kW; 380–440 V 37 kW; 500 V 45 kW; 660–690 V 22 kW |
| Rated Operational Power AC-23A (Pe) | 3-phase: 220–240 V 25 kW; 380–440 V 45 kW; 500 V 55 kW; 660–690 V 30 kW |
| Maximum Fuse Current | gG 125 A |
| Rated Short-Time Withstand Current (Icw) | 2000 A (1 s) |
| Power Loss per Pole | 3.8 W |
| Solid Conductor Cable Cross-Section | 2.5–50 mm2 |
| Stranded Conductor Cable Cross-Section | 50 mm2 |
| Flexible Conductor Cross-Section | 4–35 mm2 |
| Conductor Cross-Section with Ferrule | 2.5–35 mm2 |
| Cable section (AWG/MCM) | AWG 2 (flexible); AWG 10–1/0 (solid or stranded) |
| Conductor Material | Copper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered) |
| Tightening Torque | 3 Nm (27 lb-in) |
| Recommended Screw Driver | Pozidriv/Phillips PH2; slotted 1.2 x 6.5 mm (DIN 5264) |
| Contact Type | Rigid bridging link |
| Contact Material | Silver |
| Connection Type | Screw terminal |
| UL/CSA Rated Insulation Voltage (Ui) | 600 V AC |
| UL/CSA Thermal Current | 125 A |
| Operating Temperature | -5...+55 °C |