Cable Current-Carrying Capacity and Sizing Guide (IEC 60364-5-52)

Reference ampacity tables for copper PVC (70 °C) and XLPE (90 °C) cables under IEC / TS HD 60364-5-52 installation methods, voltage drop formulas, and breaker coordination.

Cable current-carrying capacity (Iz) is the maximum continuous RMS current a conductor can carry without exceeding the thermal limit of its insulation. Under IEC / TS HD 60364-5-52, the same copper cross-section carries substantially different current depending on insulation compound (PVC 70 °C vs XLPE 90 °C), installation method (conduit, perforated tray, buried), and ambient temperature.

> Related Category: Compare technical specifications and model options directly in the Cables, NYY Cables, and N2XH Cables categories.

Why PVC (70 °C) and XLPE (90 °C) limits change ampacity

Current flowing through copper generates I²R losses. At reference ambient conditions (30 °C in air, 20 °C in ground), maximum permissible conductor temperature depends on insulation material:

IEC 60364-5-52 reference ampacity table (Copper conductors)

Typical reference values at 30 °C air / 20 °C soil for a single circuit:

Size (mm²)B1: PVC 2-cond. (A)C: PVC 3-cond. NYY (A)C: XLPE 3-cond. N2XH (A)D2: Buried PVC NYY (A)
1.5 mm²17.517.52322
2.5 mm²24243129
4 mm²32324238
6 mm²41415447
10 mm²57577563
16 mm²767610081
25 mm²10196127104
35 mm²125119158125
50 mm²151144192148
70 mm²192184246183

Derating factors, voltage drop, and breaker coordination

Site ampacity is adjusted as Iz = Iz0 × k1 × k2 (e.g., at 40 °C ambient, `k1 ≈ 0.87` for PVC and `0.91` for XLPE; 3 touching multi-core circuits on a tray apply `k2 ≈ 0.79–0.82`). On long feeders, verify voltage drop (κ ≈ 56 m/(Ω·mm²) for copper):

Finally, enforce IEC 60364-4-43 overload coordination (`Ib ≤ In ≤ Iz`) alongside miniature circuit breaker sizing so the protective device rating In never exceeds derated cable ampacity Iz.

Frequently asked questions

How many amps can a 2.5 mm² copper cable carry?

In conduit (Method B1 at 30 °C), a 2.5 mm² PVC-insulated copper conductor has a reference ampacity of 24 A and is typically protected by a 16 A (or up to 20 A when derated conditions permit) circuit breaker.

Why does N2XH carry more current than NYY of the same size?

N2XH uses XLPE insulation rated for 90 °C continuous conductor temperature, whereas NYY uses PVC rated for 70 °C. Verify that switchgear terminals are rated for higher conductor temperatures before utilizing full 90 °C ampacity.

Is ampacity alone sufficient to size a feeder cable?

No. Feeders exceeding 30–40 m frequently require one or two cross-section steps larger to keep voltage drop within 3% (lighting) or 5% (power/motors) and to satisfy fault loop disconnection times.