TTR vs NYY Cable: What Is the Difference and Where Is Each Used?

Learn how TTR and NYY cables differ in voltage class, conductor design, flexibility and place of use, and which one to choose for each application.

Original Welibaba illustration of TTR Cables

What is the difference between TTR and NYY cable? TTR (H05VV-F) is a flexible PVC-insulated connection cable with fine-stranded conductors in the 300/500 V class; it is used for appliance, machine and extension connections. NYY (YVV) is a fixed-installation power cable in the 0.6/1 kV class with PVC insulation and a thick PVC outer sheath; it is used for building feeders, in cable trays and, with suitable protection, underground. In short, TTR is for connections that move and NYY is for fixed power distribution.

Comparison table

PropertyTTR (H05VV-F)NYY (YVV)
Rated voltage300/500 V0.6/1 kV
ConductorClass 5, fine-stranded copperClass 1 or 2, solid or stranded copper
Insulation and sheathPVC insulation, PVC outer sheathPVC insulation, thick PVC outer sheath
FlexibilitySuitable for moving connectionsFor fixed installation
Place of useIndoors; appliances, machines, extension leadsIndoors and outdoors, cable trays, underground with suitable protection
CatalogTTR CablesNYY Cables

Which one should I choose?

Cross-section and current-carrying capacity

For both cable types the current-carrying capacity depends on the cross-section, number of cores, installation method and ambient temperature, so the current a TTR and an NYY of the same cross-section can carry cannot be given as a single number. On long runs the voltage drop must also be checked. You can verify the selection with the cable ampacity and voltage drop calculators.

How to read the cable marking

The printing on the cable sheath is the safest way to tell the two types apart. TTR cables are marked H05VV-F or TTR with the number of cores and cross-section (for example 3G2.5 or 3x2.5). NYY cables are marked NYY or YVV with the 0.6/1 kV voltage class, number of cores and cross-section. Do not identify a cable by its colour or thickness alone.

Frequently asked questions

Can TTR cable be laid underground?

No. TTR is not designed for underground or permanent outdoor conditions. Underground lines use sheathed cables in the 0.6/1 kV class, such as NYY, laid with mechanical protection.

Can NYY cable be used as an extension cable?

No. The conductors of NYY are designed for fixed installation and do not withstand continuous bending. Moving connections use flexible cables such as TTR or, in severe conditions, H07RN-F.

Antigron, TTR or NYY?

Choose antigron (NYM) for flush or surface-mounted fixed indoor wiring, TTR for moving appliance and machine connections, and NYY for power lines outdoors, in cable trays and underground.

How can TTR and NYY be told apart?

Check the printing on the sheath: TTR cables are marked H05VV-F or TTR, NYY cables NYY or YVV with 0.6/1 kV. If the marking cannot be read, the conductor also gives a clue: fine-stranded in TTR, thicker strands or a solid wire in NYY.