What Is a Terminal Block? Types: DIN Rail, Junction Box and Barrier Strips

What terminal blocks do; DIN rail, junction box, barrier strip, earth, fused and disconnect terminal blocks, a size-to-current table and selection rules.

A terminal block joins two or more conductors without solder or tape, in a removable and safe contact. By place of use there are three main groups: DIN rail terminal blocks in panels (IEC 60947-7-1), junction box connectors for installation joints, and barrier (screw) terminal strips for appliance connections.

> Related Category: Browse all types and sizes in Terminal Blocks, DIN Rail Terminal Blocks and Junction Box Terminal Blocks.

1. Terminal block types

TypeMountingUse
DIN rail terminal block35 mm DIN railPanel input and output wiring, terminating field cables
Earth terminal blockDIN rail; foot contacts the railProtective conductors (green-yellow body)
Neutral terminal blockDIN rail, blue bodyCollecting neutral conductors
Fused terminal blockDIN railProtecting control and sensor lines with a glass fuse
Measuring and disconnect terminal blockDIN railTesting and shorting current transformer and metering circuits
Junction box connectorInside boxes and luminairesInstallation joints; 2–8 conductors
Barrier (screw) stripScrewed to a surface or freeLuminaire, appliance and motor connections; 12-way strips cut to length
Porcelain terminal blockFreeHigh temperature: heaters, ovens, floodlights

2. Connection technology: screw, spring, push-in

TechnologyConnectionStrengthNote
ScrewTightened with a screwdriverWide size range, high currentCan loosen under vibration; needs correct torque
SpringSpring opened with a screwdriverVibration-proof, maintenance-freeLower maximum size
Push-inFerruled or solid conductor pushed straight inFastest wiringStranded wire needs a ferrule

See Screw vs Spring vs Push-in Terminal Block Difference for a full comparison.

3. DIN rail terminal block size and current

A terminal block is named by its rated cross-section; typical rated currents per IEC 60947-7-1:

Rated cross-sectionRated current
2.5 mm²24 A
4 mm²32 A
6 mm²41 A
10 mm²57 A
16 mm²76 A
35 mm²125 A

4. Choosing junction box connectors

Twisted joints wrapped in insulating tape loosen and heat up over time and are a leading cause of fires. Quick cable splice connectors replace them.

5. Selection and wiring rules

  1. Rated cross-section must match the conductor, and rated current must be equal to or above the circuit fuse.
  2. Stranded conductors go into screw terminals with a ferrule; for sizes see the DIN Rail Terminal Block, Ferrule and Cable Lug Guide.
  3. One conductor per clamping point; for two, use a double-entry terminal or a twin ferrule.
  4. Strip to the length printed on the terminal; too long leaves bare copper, too short traps insulation in the contact.
  5. Aluminium conductors need terminals marked as suitable for aluminium.
  6. Above 100 °C ambient use porcelain terminal blocks and heat-resistant cable.

Frequently asked questions

What does a terminal block do?

It joins cables to each other or to a device without solder, removably and safely, keeping panels tidy and making maintenance and fault finding easier.

What is the difference between a DIN rail terminal block and a junction box connector?

A DIN rail terminal block mounts on rail in a panel and terminates incoming and outgoing wires one by one. A junction box connector is not rail-mounted; it joins several conductors at one point inside a box or luminaire.

How many amps does a 2.5 mm² terminal block carry?

Per IEC 60947-7-1 a 2.5 mm² DIN rail terminal block is rated 24 A. The exact figure is on the maker's label.

Is a ferrule required on stranded wire?

Yes for screw and push-in terminals; it holds the strands together and secures contact. Lever connectors and most spring terminals accept stranded wire without one.

Why does a terminal block overheat or melt?

The usual cause is a loose connection: contact resistance rises and the point heats up. Other causes are an undersized terminal and more than one conductor in a clamping point.