Kraus & Naimer C42 A341-E+S1V840G/D6 On-Off Cam Switch, 5-Pole, 63 A, 64 x 64 mm Front Plate

Kraus & Naimer C42 A341-E+S1V840G/D6 On-Off Cam Switch, 5-Pole, 63 A, 64 x 64 mm Front Plate

Kraus & Naimer C42 A341-E+S1V840G/D6 is a 63 A (Ith) C42 series cam switch; function: 5-pole on-off (0-1) switch (lift switch). Mounting: E mounting (four-hole panel), 64 x 64 mm front plate; the S1 V840G extra is a padlock device for 3 padlocks (7–8 mm shackle). Switching function: positions 0-1; switching angle 60°; 3 contact stages. Ratings: rated insulation voltage Ui 690 V, impulse withstand voltage Uimp 6 kV (switch) / 4 kV (switch disconnector), AC-21A 63 A, three-phase motor rating at 380–440 V: AC-3 18.5 kW, AC-23A 30 kW, breaking capacity 550 / 550 / 365 A (220–240 / 380–440 / 660–690 V), maximum fuse 80 A gG, short-time withstand current 1000 A (1 s). Connection: flexible conductors 4–10 mm², solid or stranded conductors 1.5–16 mm², terminal tightening torque 3 Nm. It is used to switch the supply circuit of a lift on and off (0-1).

Size TypeS1
Number of Poles5P
SeriesC42
Function CodeA341
Switch FunctionAç-Kapa (0-1)
Switch Positions0-1
Number of Positions2
Switching Angle60° °
Number of Levels3
Front Plate CodeF070
Front Plate Size (A x B)64 x 64 mm
Rated Current63 A
Conventional Free Air Thermal Current (Ith)63 A
Ambient temperature for rated current55 °C (24 hours, tepe 60 °C)
Conventional Enclosed Thermal Current (Ithe)63 A
Rated Insulation Voltage (Ui)690 V (AC 50/60 Hz)
Rated Impulse Withstand Voltage (Uimp)6 kV (circuit breaker); 4 kV (switch-disconnector)
Overvoltage categoryIII
Pollution Degree3
Rated Operational Current AC-15 (Ie)220–240 V: 16 A; 380–440 V: 7 A
Rated Operational Current AC-20A (Ie)690 V: 63 A
Rated Operational Current AC-21A (Ie)20–690 V: 63 A
Rated Operational Current AC-22A (Ie)220–500 V: 63 A; 660–690 V: 63 A
Rated Operational Power AC-2 (Pe)3-phase: 220–240 V 18.5 kW; 380–440 V 30 kW; 500 V 40 kW; 660–690 V 37 kW
Rated Operational Power AC-3 (Pe)3-phase: 220–240 V 11 kW; 380–440 V 18.5 kW; 500 V 18.5 kW; 660–690 V 18.5 kW. 1-phase: 110–120 V 3 kW; 220–240 V 6 kW; 380–440 V 11 kW
Rated Operational Power AC-4 (Pe)3-phase: 220–240 V 5.5 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 110–120 V 1.2 kW; 220–240 V 2.4 kW; 380–440 V 4 kW
Rated Operational Power AC-23A (Pe)3-phase: 220–240 V 15 kW; 380–440 V 30 kW; 500 V 45 kW; 660–690 V 40 kW. 1-phase: 110–120 V 4 kW; 220–240 V 10 kW; 380–440 V 18.5 kW
Maximum Fuse CurrentgG 80 A
Rated Short-Time Withstand Current (Icw)1000 A (1 s)
Breaking Capacity220–240 V: 550 A; 380–440 V: 550 A; 660–690 V: 365 A
Power Loss per Pole1.7 W
Solid Conductor Cable Cross-Section1.5–16 mm2
Stranded Conductor Cable Cross-Section2x16 mm2
Flexible Conductor Cross-Section4–10 mm2
Conductor Cross-Section with Ferrule2.5–10 mm2
Cable section (AWG/MCM)AWG 6
Conductor MaterialCopper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered)
Tightening Torque3 Nm (26.4 lb-in)
Recommended Screw DriverPozidriv/Phillips PH3; slotted 1.6 x 8 mm (DIN 5264)
Contact TypeRigid bridging link