Kraus & Naimer C42 A400 Motor Reversing Cam Switch, 2-Pole, 63 A, 64 x 64 mm Front Plate

Kraus & Naimer C42 A400 Motor Reversing Cam Switch, 2-Pole, 63 A, 64 x 64 mm Front Plate

Kraus & Naimer C42 A400 is a 2-pole (single-phase), 63 A motor reversing cam switch with 1-0-2 positions. Technical values: C42 type, size class S1, 64 x 64 mm front plate; thermal current Ith 63 A (55 °C), enclosed thermal current Ithe 63 A; rated insulation voltage Ui 690 V, rated impulse withstand voltage Uimp 6 kV (switch), 4 kV (switch disconnector); AC-21A 63 A, AC-22A 63 A, AC-15 380–440 V 7 A; single-phase motor rating at 220–240 V: AC-3 6 kW, AC-23A 10 kW; maximum gG 80 A fuse, Icw 1000 A (1 s); conductor cross-section: solid 1.5–16 mm², flexible 4–10 mm²; tightening torque 3 Nm; 2 poles, 2 levels, positions 1-0-2, switching angle 60°. Values are given in accordance with IEC 60947-3 and EN 60947-3. It is used to reverse the direction of single-phase motors; the centre 0 position stops the motor.

Size TypeS1
Number of Poles2P
SeriesC42
Function CodeA400
Switch FunctionMotor Enversörü (1-0-2)
Switch Positions1-0-2
Number of Positions3
Switching Angle60° °
Number of Levels2
Front Plate CodeF071
Front Plate Size (A x B)64 x 64 mm
Rated Current63 A
Conventional Free Air Thermal Current (Ith)63 A
Ambient temperature for rated current55 °C (24 hours, tepe 60 °C)
Conventional Enclosed Thermal Current (Ithe)63 A
Rated Insulation Voltage (Ui)690 V (AC 50/60 Hz)
Rated Impulse Withstand Voltage (Uimp)6 kV (circuit breaker); 4 kV (switch-disconnector)
Overvoltage categoryIII
Pollution Degree3
Rated Operational Current AC-15 (Ie)220–240 V: 16 A; 380–440 V: 7 A
Rated Operational Current AC-20A (Ie)690 V: 63 A
Rated Operational Current AC-21A (Ie)20–690 V: 63 A
Rated Operational Current AC-22A (Ie)220–500 V: 63 A; 660–690 V: 63 A
Rated Operational Power AC-2 (Pe)3-phase: 220–240 V 18.5 kW; 380–440 V 30 kW; 500 V 40 kW; 660–690 V 37 kW
Rated Operational Power AC-3 (Pe)3-phase: 220–240 V 11 kW; 380–440 V 18.5 kW; 500 V 18.5 kW; 660–690 V 18.5 kW. 1-phase: 110–120 V 3 kW; 220–240 V 6 kW; 380–440 V 11 kW
Rated Operational Power AC-4 (Pe)3-phase: 220–240 V 5.5 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 110–120 V 1.2 kW; 220–240 V 2.4 kW; 380–440 V 4 kW
Rated Operational Power AC-23A (Pe)3-phase: 220–240 V 15 kW; 380–440 V 30 kW; 500 V 45 kW; 660–690 V 40 kW. 1-phase: 110–120 V 4 kW; 220–240 V 10 kW; 380–440 V 18.5 kW
Maximum Fuse CurrentgG 80 A
Rated Short-Time Withstand Current (Icw)1000 A (1 s)
Breaking Capacity220–240 V: 550 A; 380–440 V: 550 A; 660–690 V: 365 A
Power Loss per Pole1.7 W
Solid Conductor Cable Cross-Section1.5–16 mm2
Stranded Conductor Cable Cross-Section2x16 mm2
Flexible Conductor Cross-Section4–10 mm2
Conductor Cross-Section with Ferrule2.5–10 mm2
Cable section (AWG/MCM)AWG 6
Conductor MaterialCopper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered)
Tightening Torque3 Nm (26.4 lb-in)
Recommended Screw DriverPozidriv/Phillips PH3; slotted 1.6 x 8 mm (DIN 5264)
Contact TypeRigid bridging link