Kraus & Naimer CA20 A212 Changeover Cam Switch, 3-Pole, 25 A, 48 x 48 mm Front Plate

Kraus & Naimer CA20 A212 Changeover Cam Switch, 3-Pole, 25 A, 48 x 48 mm Front Plate

Kraus & Naimer CA20 A212 is a 3-pole changeover (1-0-2) cam switch rated 25 A. The CA20 type switch has a 48 x 48 mm front plate; Ith 25 A, Ui 690 V; three-phase motor rating at 380–440 V is 7.5 kW (AC-3) and 11 kW (AC-23A); rated short-time withstand current Icw is 280 A (1 s); terminals accept conductors up to 4 mm². Function: 3 poles, 3 positions (1-0-2), 60° switching angle, 3 stages. This changeover switch is used to switch between two circuits or supplies; both circuits are open in the centre (0) position.

Size TypeS0
Number of Poles3P
SeriesCA20
Function CodeA212
Switch FunctionEnversör (1-0-2)
Switch Positions1-0-2
Number of Positions3
Switching Angle60° °
Number of Levels3
Front Plate CodeF071
Front Plate Size (A x B)48 x 48 mm
Rated Current25 A
Conventional Free Air Thermal Current (Ith)25 A
Ambient temperature for rated current55 °C (24 hours, tepe 60 °C)
Conventional Enclosed Thermal Current (Ithe)25 A
Rated Insulation Voltage (Ui)690 V (AC 50/60 Hz)
Rated Impulse Withstand Voltage (Uimp)6 kV
Overvoltage categoryIII
Pollution Degree3
Rated Operational Current AC-15 (Ie)220–240 V: 8 A; 380–440 V: 5 A
Rated Operational Current AC-20A (Ie)690 V: 25 A
Rated Operational Current AC-21A (Ie)20–690 V: 25 A
Rated Operational Current AC-22A (Ie)220–500 V: 25 A; 660–690 V: 25 A
Rated Operational Power AC-2 (Pe)3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 15 kW; 660–690 V 13 kW
Rated Operational Power AC-3 (Pe)3-phase: 220–240 V 4 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 110–120 V 1.5 kW; 220–240 V 3 kW; 380–440 V 3.7 kW
Rated Operational Power AC-4 (Pe)3-phase: 220–240 V 1.5 kW; 380–440 V 3 kW; 500 V 3 kW; 660–690 V 3 kW. 1-phase: 110–120 V 0.45 kW; 220–240 V 1.1 kW; 380–440 V 2.2 kW
Rated Operational Power AC-23A (Pe)3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 11 kW; 660–690 V 11 kW. 1-phase: 110–120 V 1.5 kW; 220–240 V 3 kW; 380–440 V 5.5 kW
Maximum Fuse CurrentgG 35 A
Rated Short-Time Withstand Current (Icw)280 A (1 s)
Breaking Capacity220–240 V: 200 A; 380–440 V: 200 A; 660–690 V: 125 A
Power Loss per Pole0.9 W
Solid Conductor Cable Cross-Section0.75–4 mm2
Stranded Conductor Cable Cross-Section2x4 mm2
Flexible Conductor Cross-Section1.5–4 mm2
Conductor Cross-Section with Ferrule1–2.5 mm2
Cable section (AWG/MCM)AWG 12 (flexible); AWG 10 (solid or stranded)
Conductor MaterialCopper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered)
Tightening Torque1 Nm (9 lb-in)
Recommended Screw DriverPozidriv/Phillips PH1; slotted 0.8 x 5.5 mm (DIN 5264)
Contact TypeRigid bridging link