Kraus & Naimer CA20 A223 Changeover Cam Switch without OFF, 4-Pole, 25 A, 48 x 48 mm Front Plate

Kraus & Naimer CA20 A223 Changeover Cam Switch without OFF, 4-Pole, 25 A, 48 x 48 mm Front Plate

Kraus & Naimer CA20 A223 is a 4-pole changeover cam switch (1-2, without off position) rated 25 A. The CA20 type switch has a 48 x 48 mm front plate; Ith 25 A, Ui 690 V; three-phase motor rating at 380–440 V is 7.5 kW (AC-3) and 11 kW (AC-23A); rated short-time withstand current Icw is 280 A (1 s); terminals accept conductors up to 4 mm². Function: 4 poles, 2 positions (1-2), 60° switching angle, 4 stages. This changeover switch is used to switch between two circuits without an off position.

Size TypeS0
Number of Poles4P
SeriesCA20
Function CodeA223
Switch FunctionSıfırsız Enversör (1-2)
Switch Positions1-2
Number of Positions2
Switching Angle60° °
Number of Levels4
Front Plate CodeF072
Front Plate Size (A x B)48 x 48 mm
Rated Current25 A
Conventional Free Air Thermal Current (Ith)25 A
Ambient temperature for rated current55 °C (24 hours, tepe 60 °C)
Conventional Enclosed Thermal Current (Ithe)25 A
Rated Insulation Voltage (Ui)690 V (AC 50/60 Hz)
Rated Impulse Withstand Voltage (Uimp)6 kV
Overvoltage categoryIII
Pollution Degree3
Rated Operational Current AC-15 (Ie)220–240 V: 8 A; 380–440 V: 5 A
Rated Operational Current AC-20A (Ie)690 V: 25 A
Rated Operational Current AC-21A (Ie)20–690 V: 25 A
Rated Operational Current AC-22A (Ie)220–500 V: 25 A; 660–690 V: 25 A
Rated Operational Power AC-2 (Pe)3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 15 kW; 660–690 V 13 kW
Rated Operational Power AC-3 (Pe)3-phase: 220–240 V 4 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 110–120 V 1.5 kW; 220–240 V 3 kW; 380–440 V 3.7 kW
Rated Operational Power AC-4 (Pe)3-phase: 220–240 V 1.5 kW; 380–440 V 3 kW; 500 V 3 kW; 660–690 V 3 kW. 1-phase: 110–120 V 0.45 kW; 220–240 V 1.1 kW; 380–440 V 2.2 kW
Rated Operational Power AC-23A (Pe)3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 11 kW; 660–690 V 11 kW. 1-phase: 110–120 V 1.5 kW; 220–240 V 3 kW; 380–440 V 5.5 kW
Maximum Fuse CurrentgG 35 A
Rated Short-Time Withstand Current (Icw)280 A (1 s)
Breaking Capacity220–240 V: 200 A; 380–440 V: 200 A; 660–690 V: 125 A
Power Loss per Pole0.9 W
Solid Conductor Cable Cross-Section0.75–4 mm2
Stranded Conductor Cable Cross-Section2x4 mm2
Flexible Conductor Cross-Section1.5–4 mm2
Conductor Cross-Section with Ferrule1–2.5 mm2
Cable section (AWG/MCM)AWG 12 (flexible); AWG 10 (solid or stranded)
Conductor MaterialCopper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered)
Tightening Torque1 Nm (9 lb-in)
Recommended Screw DriverPozidriv/Phillips PH1; slotted 0.8 x 5.5 mm (DIN 5264)
Contact TypeRigid bridging link

Shipping & assurance

For made-to-order products, the procurement and carrier hand-over time is shared with the quotation.

In rare cases, all or part of an order may be unavailable due to stock or procurement updates. In this case, the customer is informed and the relevant product is cancelled and refunded. A product being open for sale does not guarantee that it is in physical store stock.

Delivery and returns