Kraus & Naimer CA20 T203/01 EG Emergency Stop Main Switch, 3-Pole, 25 A

Kraus & Naimer CA20 T203/01 EG Emergency Stop Main Switch, 3-Pole, 25 A

Kraus & Naimer CA20 T203/01 EG is a 25 A (Ith), 3-pole emergency stop main switch (lockable, red handle, yellow front plate); EG mounting (four-hole panel, larger front plate and handle, heavy-duty latching), IP40. Ratings: rated insulation voltage Ui 690 V, impulse withstand voltage Uimp 6 kV, AC-21A 25 A, three-phase motor rating at 380–440 V: AC-3 7.5 kW, AC-23A 11 kW, breaking capacity 200 / 200 / 125 A (220–240 / 380–440 / 660–690 V), maximum fuse 35 A gG, short-time withstand current 280 A (1 s). Connection: flexible conductors 1.5–4 mm², solid or stranded conductors 0.75–4 mm², terminal tightening torque 1 Nm. It is used as a three-phase 0-1 main switch; this is the yellow-red lockable version.

Number of Poles3P
Rated Current25 A
Mounting TypeEG montajı: dört delikli panel, büyük ön plaka and kol, ağır hizmet mandalı
IP RatingIP40
SeriesCA20
Size TypeS0
Function CodeT203
Switch FunctionAcil Durdurma Fonksiyonlu Ana Şalter (0-1)
Switch Positions0-1
Number of Positions2
Handle ColorRed (sarı ön plaka)
Conventional Free Air Thermal Current (Ith)25 A
Ambient temperature for rated current55 °C (24 hours, tepe 60 °C)
Conventional Enclosed Thermal Current (Ithe)25 A
Rated Insulation Voltage (Ui)690 V (AC 50/60 Hz and DC)
Rated Impulse Withstand Voltage (Uimp)6 kV
Overvoltage categoryIII
Pollution Degree3
Rated Operational Current AC-15 (Ie)220–240 V: 8 A; 380–440 V: 5 A
Rated Operational Current AC-20A (Ie)690 V: 25 A
Rated Operational Current AC-21A (Ie)20–690 V: 25 A
Rated Operational Current AC-22A (Ie)220–500 V: 25 A; 660–690 V: 25 A
Rated Operational Power AC-2 (Pe)3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 15 kW; 660–690 V 13 kW
Rated Operational Power AC-3 (Pe)3-phase: 220–240 V 4 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 110–120 V 1.5 kW; 220–240 V 3 kW; 380–440 V 3.7 kW
Rated Operational Power AC-4 (Pe)3-phase: 220–240 V 1.5 kW; 380–440 V 3 kW; 500 V 3 kW; 660–690 V 3 kW. 1-phase: 110–120 V 0.45 kW; 220–240 V 1.1 kW; 380–440 V 2.2 kW
Rated Operational Power AC-23A (Pe)3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 11 kW; 660–690 V 11 kW. 1-phase: 110–120 V 1.5 kW; 220–240 V 3 kW; 380–440 V 5.5 kW
Maximum Fuse CurrentgG 35 A
Rated Short-Time Withstand Current (Icw)280 A (1 s)
Breaking Capacity220–240 V: 200 A; 380–440 V: 200 A; 660–690 V: 125 A
Power Loss per Pole0.9 W
Solid Conductor Cable Cross-Section0.75–4 mm2
Stranded Conductor Cable Cross-Section2x4 mm2
Flexible Conductor Cross-Section1.5–4 mm2
Conductor Cross-Section with Ferrule1–2.5 mm2
Cable section (AWG/MCM)AWG 12 (flexible); AWG 10 (solid or stranded)
Conductor MaterialCopper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered)
Tightening Torque1 Nm (9 lb-in)
Recommended Screw DriverPozidriv/Phillips PH1; slotted 0.8 x 5.5 mm (DIN 5264)
Contact TypeRigid bridging link
Contact MaterialSilver