Kraus & Naimer KG100 T203/40 KL71V Emergency Stop Main Switch, 3-Pole, 100 A, in Enclosure (KL71V)
- Brand: Kraus & Naimer
- SKU: KG100 T203/40 KL71V
- GTIN: 9004257074617
- MPN: KG100 T203/40 KL71V
- Model: 100 A
- Price: 14536.56 TRY + VAT · incl. VAT 17443.87 TRY
- Availability: Made to order
- Load Break Switches
- Kraus & Naimer Load Break Switches
- Selection guide: What Is a Load Break Switch? Types and Selection Criteria
Kraus & Naimer KG100 T203/40 KL71V is a 100 A (Ith), 3-pole emergency stop main switch (red handle, yellow front plate); supplied as a maintenance and safety switch in a KL series plastic enclosure (KL71V), IP66/67, enclosure size 250 x 145 x 107 mm. Ratings: rated insulation voltage Ui 690 V, impulse withstand voltage Uimp 6 kV, AC-21A 100 A, three-phase motor rating at 380–440 V: AC-3 30 kW, AC-23A 37 kW, breaking capacity 700 / 650 / 280 A (220–240 / 380–440 / 660–690 V), maximum fuse 100 A gG, short-time withstand current 1850 A (1 s). Connection: flexible conductors 4–35 mm², solid or stranded conductors 2.5–50 mm², terminal tightening torque 3 Nm. The enclosure has IP66/67 protection and is flame resistant to UL94 V-0; a ground terminal and a safety interlocked cover are standard equipment. It includes 1 NO + 1 NC auxiliary contacts; the auxiliary contacts close after the main contacts close and open before the main contacts open. The KG and C316 series switches exceed the requirements of IEC 60947-3 / EN 60947-3 (VDE 0660 part 107), IEC/EN 60204 and VDE 0113 and are used as switch disconnectors, main switches and maintenance switches.
| Number of Poles | 3P |
|---|---|
| Rated Current | 100 A |
| Mounting Type | KL71V ile kutulu (bakım and emniyet şalteri) |
| IP Rating | IP66/67 |
| Series | KG100 |
| Size Type | S1 |
| Function Code | T203 |
| Switch Function | Acil Durdurma Fonksiyonlu Ana Şalter (0-1) |
| Switch Positions | 0-1 |
| Number of Positions | 2 |
| Handle Color | Red (sarı ön plaka) |
| Conventional Free Air Thermal Current (Ith) | 100 A |
| Ambient temperature for rated current | 50 °C (24 hours, tepe 55 °C) |
| Conventional Enclosed Thermal Current (Ithe) | 100 A |
| Rated Insulation Voltage (Ui) | 690 V (AC 50/60 Hz) |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Overvoltage category | III |
| Pollution Degree | 3 |
| Rated Operational Current AC-20A (Ie) | 690 V: 100 A |
| Rated Operational Current AC-21A (Ie) | 20–690 V: 100 A |
| Rated Operational Current AC-22A (Ie) | 220–500 V: 100 A; 660–690 V: 85 A |
| Rated Operational Power AC-3 (Pe) | 3-phase: 220–240 V 18.5 kW; 380–440 V 30 kW; 500 V 37 kW; 660–690 V 22 kW |
| Rated Operational Power AC-23A (Pe) | 3-phase: 220–240 V 22 kW; 380–440 V 37 kW; 500 V 45 kW; 660–690 V 30 kW |
| Maximum Fuse Current | gG 100 A |
| Rated Short-Time Withstand Current (Icw) | 1850 A (1 s) |
| Breaking Capacity | 220–240 V: 700 A; 380–440 V: 650 A; 660–690 V: 280 A |
| Power Loss per Pole | 2.4 W |
| Solid Conductor Cable Cross-Section | 2.5–50 mm2 |
| Stranded Conductor Cable Cross-Section | 50 mm2 |
| Flexible Conductor Cross-Section | 4–35 mm2 |
| Conductor Cross-Section with Ferrule | 2.5–35 mm2 |
| Cable section (AWG/MCM) | AWG 2 (flexible); AWG 10–1/0 (solid or stranded) |
| Conductor Material | Copper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered) |
| Tightening Torque | 3 Nm (27 lb-in) |
| Recommended Screw Driver | Pozidriv/Phillips PH2; slotted 1.2 x 6.5 mm (DIN 5264) |
| Contact Type | Rigid bridging link |
| Contact Material | Silver |
| Connection Type | Screw terminal |
| UL/CSA Rated Insulation Voltage (Ui) | 600 V AC |
| UL/CSA Thermal Current | 100 A |
Shipping & assurance
For made-to-order products, the procurement and carrier hand-over time is shared with the quotation.
In rare cases, all or part of an order may be unavailable due to stock or procurement updates. In this case, the customer is informed and the relevant product is cancelled and refunded. A product being open for sale does not guarantee that it is in physical store stock.