Schneider Electric LC1D25P7 TeSys Deca Contactor 3P (3NO) 25A AC-3 230V AC

Schneider Electric LC1D25P7 TeSys Deca Contactor 3P (3NO) 25A AC-3 230V AC

LC1D25P7 is a 3-pole (3NO) TeSys D contactor with a 230 V 50/60 Hz AC coil, used in motor control applications up to 25 A / 690 V (11 kW at 400 V) in AC-3/3e. Electrical characteristics: rated current 25 A; rated operational current (Ie) 25 A (below 60 °C), ≤ 440 V AC AC-3, for the power circuit / 40 A (below 60 °C), ≤ 440 V AC AC-1, for the power circuit / 25 A (below 60 °C), ≤ 440 V AC AC-3e, for the power circuit; utilization category AC-3 / AC-3e / AC-1 / AC-4; rated operational voltage (Ue) power circuit: ≤ 690 V AC 25…400 Hz / power circuit: ≤ 300 V DC; rated impulse withstand voltage (Uimp) 6 kV (IEC 60947); rated control circuit voltage (Uc) 230 V AC 50/60 Hz; power pole contact arrangement 3 NO; auxiliary contact configuration 1 NO + 1 NC; conventional free air thermal current (Ith) 10 A (60 °C), for the signalling circuit / 40 A (60 °C), for the power circuit; maximum operating rate (cycles/h) 3600 cycles/h, 60 °C; mechanical endurance 15 million cycles; power loss per pole 3.2 W AC-1 / 1.25 W AC-3 / 1.25 W AC-3e; hold-in power consumption (VA) 7.5 VA 60 Hz cos phi 0.3 (20 °C) / 7 VA 50 Hz cos phi 0.3 (20 °C); inrush power (VA) 70 VA 60 Hz cos phi 0.75 (20 °C) / 70 VA 50 Hz cos phi 0.75 (20 °C). Mechanical and environmental characteristics: dimensions 45 x 85 x 92 mm (W x H x D); product weight 0.37 kg; mounting support rail / plate; IP rating IP20 front face (IEC 60529); operating ambient temperature up to 60 °C; operating altitude 0…3000 m; fire resistance 850 °C (IEC 60695-2-1); certifications UL / CCC / CSA / Denizcilik / UKCA / EAC / CB Scheme. It is used in resistive load and motor control applications and mounts on a DIN rail or by screw fixing.

Current25 A
Number of Poles3P
SeriesTeSys Deca (TeSys D)
Product Weight0.37 kg
StandardsCSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1
Rated Insulation Voltage (Ui)Güç devresi: 690 V (IEC 60947-4-1); Güç devresi: 600 V CSA sertifikali; Güç devresi: 600 V UL sertifikali; Sinyalleme devresi: 690 V (IEC 60947-1); Sinyalleme devresi: 600 V CSA sertifikali; Sinyalleme devresi: 600 V UL sertifikali
Rated Impulse Withstand Voltage (Uimp)6 kV (IEC 60947)
Width45 mm
IP RatingIP20 ön yüz (IEC 60529)
Height85 mm
Tightening TorqueKontrol devresi: 1.7 N.m - üzerinde Screw clamp terminals - tornavidayla düz Ø 6 mm; Kontrol devresi: 1.7 N.m - üzerinde Screw clamp terminals - tornavidayla Philips No 2; Güç devresi: 2.5 N.m - üzerinde Screw clamp terminals - tornavidayla düz Ø 6 mm; Güç devresi: 2.5 N.m - üzerinde Screw clamp terminals - tornavidayla Philips No 2; Kontrol devresi: 1.7 N.m - üzerinde Screw clamp terminals - tornavidayla pozidriv No 2; Güç devresi: 2.5 N.m - üzerinde Screw clamp terminals - tornavidayla pozidriv No 2
Depth92 mm
Mechanical Life15 milyon cycles
Electrical Life1.65 milyon cycles 25 A AC-3 Ue'de ≤ 440 V; 1.4 milyon cycles 40 A AC-1 Ue'de ≤ 440 V; 1.65 milyon cycles 25 A AC-3e Ue'de ≤ 440 V
CertificationsUL; CCC; CSA; Denizcilik; UKCA; EAC; CB Şeması
Conventional Free Air Thermal Current (Ith)10 A (60 °C), sinyalleme devresi için; 40 A (60 °C), güç devresi için
Contactor ApplicationDirenç yükü; Motor kontrol
Utilization CategoryAC-3; AC-3e; AC-1; AC-4
Operating VoltageGüç devresi: ≤ 690 V AC 25…400 Hz; Güç devresi: ≤ 300 V DC
Rated Operational Current (Ie)25 A (60 °C altında), ≤ 440 V AC AC-3, güç devresi için; 40 A (60 °C altında), ≤ 440 V AC AC-1, güç devresi için; 25 A (60 °C altında), ≤ 440 V AC AC-3e, güç devresi için
Power Pole Contact Arrangement3 NA
Rated Making Capacity (Irms)140 A AC, sinyalleme devresi için (IEC 60947-5-1); 250 A DC, sinyalleme devresi için (IEC 60947-5-1); 450 A, 440 V, güç devresi için (IEC 60947)
Rated Breaking Capacity450 A, 440 V, güç devresi için (IEC 60947)
Power Loss per Pole3.2 W AC-1; 1.25 W AC-3; 1.25 W AC-3e
Control Circuit TypeAC (50/60 Hz standart)
Operating Time12…22 msn kapama; 4…19 msn açma
Maximum Operating Rate (cycles/h)3600 cycles/saat, 60 °C
Auxiliary Contact1 NA + 1 NK
Rated Short-Time Withstand Current (Icw)240 A 40 °C - 10 s, güç devresi için; 380 A 40 °C - 1 s, güç devresi için; 50 A 40 °C - 10 min, güç devresi için; 120 A 40 °C - 1 min, güç devresi için; 100 A - 1 s, sinyalleme devresi için; 120 A - 500 ms, sinyalleme devresi için; 140 A - 100 ms, sinyalleme devresi için
Control Voltage230 V AC 50/60 Hz
Motor Power (kW)5.5 kW, 220/230 V AC 50/60 Hz (AC-3); 11 kW, 380/400 V AC 50/60 Hz (AC-3); 11 kW, 415/440 V AC 50/60 Hz (AC-3); 15 kW, 500 V AC 50/60 Hz (AC-3); 15 kW, 660/690 V AC 50/60 Hz (AC-3); 5.5 kW, 220/230 V AC 50/60 Hz (AC-3e); 11 kW, 380/400 V AC 50/60 Hz (AC-3e); 11 kW, 415/440 V AC 50/60 Hz (AC-3e); 15 kW, 500 V AC 50/60 Hz (AC-3e); 15 kW, 660/690 V AC 50/60 Hz (AC-3e); 5.5 kW, 400 V AC 50/60 Hz (AC-4)
Pollution Degree3
Product TypeContactor
Operating Altitude0…3000 m
Overvoltage categoryIII
Control Circuit Voltage Limits0.3...0.6 Uc (-40...70 °C):düşme AC 50/60 Hz; 0.8...1.1 Uc (-40...60 °C):çalışma AC 50 Hz; 0.85...1.1 Uc (-40...60 °C):çalışma AC 60 Hz; 1...1.1 Uc (60...70 °C):çalışma AC 50/60 Hz
Mounting SupportRay; Plaka
Fire Resistance850 °C (IEC 60695-2-1)
Motor Power (HP)3 hp, 230/240 V AC 50/60 Hz, 1 fazlı motorlar için; 2 hp, 115 V AC 50/60 Hz, 1 fazlı motorlar için; 7.5 hp, 230/240 V AC 50/60 Hz, 3 fazlı motorlar için; 15 hp, 460/480 V AC 50/60 Hz, 3 fazlı motorlar için; 20 hp, 575/600 V AC 50/60 Hz, 3 fazlı motorlar için; 7.5 hp, 200/208 V AC 50/60 Hz, 3 fazlı motorlar için
Protective CoverAvailable