What Is a Fuse? Fuse Types: MCB, NH Blade, Cartridge and Glass Fuses

What a fuse does, how a miniature circuit breaker differs from a fuse link, NH blade, cylindrical cartridge, D-type and glass fuses, gG vs aM classes and selection rules.

A fuse is a protective device that opens a circuit by itself when current exceeds the permitted value; it protects cables from overheating and installations from short-circuit damage. There are two main groups: fuse links (IEC 60269), whose element melts and must be replaced, and miniature circuit breakers (IEC 60898-1), which can be reset after tripping.

> Related Category: Browse all types and ratings in Fuses, Miniature Circuit Breakers and Blade Fuses.

1. Fuse types compared

TypeCurrent rangeBreaking capacityAfter operationTypical use
Miniature circuit breaker (MCB)1–125 A3 – 4.5 – 6 – 10 kAReset the toggleHome and commercial boards, lighting and socket circuits
RCBO6–63 A4.5–10 kAReset the toggleOvercurrent plus residual current protection in one device
NH blade fuse2–1,250 A100–120 kAReplace the linkMain board incomers, transformer outputs, industrial distribution
Cylindrical cartridge fuse0.5–125 A50–120 kAReplace the cartridgeControl circuits, motors, semiconductors, solar strings
D-type (bottle) fuse2–63 A50 kAReplace the linkOlder building installations, meter boards
Glass fuse0.05–20 A35 A – 1.5 kAReplaceElectronics, inside appliances, instruments

2. Miniature circuit breakers

An MCB has two releases: a bimetal (thermal) strip that bends on overload and a coil (magnetic) that acts instantly on short circuit. The curve letter gives the magnetic trip multiple: B (3–5 times), C (5–10 times), D (10–20 times). See MCB B, C, D Tripping Curve Difference.

3. NH blade fuses

Ceramic body, quartz sand filling and blade contacts; fitted in a fuse base or fuse switch-disconnector. They limit and clear very high fault currents within milliseconds.

NH sizeCurrent range
000 / 002–160 A
116–250 A
235–400 A
3315–630 A
4500–1,250 A

A link fits only a blade fuse base of the same size and is pulled off-load with an insulated fuse handle.

4. Cylindrical cartridge and glass fuses

Cylindrical cartridge fuses are named by diameter × length and sit in DIN-rail fuse holders:

Size (mm)Maximum current
8.5 × 31.520 A
10 × 3832 A
14 × 5150 A
22 × 58125 A

Solar strings use 10 × 38 gPV cartridges rated 1,000 V DC; an AC cartridge cannot quench a DC arc. Glass fuses (5 × 20 mm and 6.3 × 32 mm) serve electronics and carry a speed letter: F fast, T time-lag.

5. What do gG and aM mean?

ClassRangeUse
gGOverload + short circuit (full range)Cable and general line protection
aMShort circuit only (partial range)Motor circuits; rides through starting current, needs an overload relay
gR / aRVery fastSemiconductors in drives, UPS units and rectifiers
gPVDC, full rangePhotovoltaic strings

6. Selecting and connecting a fuse

Basic rule: load current ≤ fuse rating ≤ cable current-carrying capacity. The fuse protects the cable, so it is sized for the cable, not the appliance.

Copper cable sizeTypical fuseCircuit
1.5 mm²10 ALighting
2.5 mm²16 ASockets
4 mm²20–25 AOven, air conditioner, water heater
6 mm²32 AHob, sub-main

Frequently asked questions

What does a fuse do?

It opens the circuit when current exceeds a set value, preventing cables from overheating and a short circuit from turning into a fire.

What is the difference between an MCB and an NH blade fuse?

An MCB is reset by its toggle after tripping and is made up to 125 A. An NH fuse link melts and must be replaced, but covers currents up to 1,250 A and faults up to 120 kA.

Why does a fuse blow or a breaker trip?

Three causes: overload (too many loads on one circuit), short circuit (line to neutral or line to earth), and heating from ageing or a loose terminal. If the RCD trips, the cause is earth leakage.

Can an aM fuse replace a gG fuse?

No. An aM fuse gives no overload protection; it clears short circuits only and is used with an overload relay in motor circuits. Cable protection needs gG.

How many watts can a 16 A breaker carry?

On a 230 V single-phase circuit, 16 × 230 ≈ 3,680 W. Continuous loads should stay near 80% of that (2,900 W).