Kraus & Naimer C26 A441/TRA301 Two-Speed (Dahlander) Cam Switch, 3-Pole, 32 A, in Enclosure (KE03)
- Brand: Kraus & Naimer
- SKU: C26 A441/TRA301
- MPN: C26 A441/TRA301
- Model: 32 A
- Price: 5652.00 TRY + VAT · incl. VAT 6782.40 TRY
- Availability: Made to order
- Two-Speed Dahlander Switches
- Kraus & Naimer Two-Speed Dahlander Switches
- Selection guide: What Is a Dahlander Switch? Two-Speed Motor Switch Types and Selection
Kraus & Naimer C26 A441/TRA301 is a 3-pole, 32 A two-speed (Dahlander) cam switch for single-winding motors. The switch has positions 1-0-2, a switching angle of 60° and 4 levels. It is supplied as an enclosed (TRA) version in a KE03 enclosure (IP65) with an I handle. Front plate code F071; size type S1. Rated insulation voltage is 690 V (AC 50/60 Hz) and rated impulse withstand voltage is 6 kV. AC-21A rated operational current is 32 A over 20–690 V; three-phase AC-3 rated power (380–440 V) is 11 kW; AC-23A rated power (380–440 V) is 15 kW. Maximum fuse rating gG 50 A; rated short-time withstand current 350 A (1 s); power loss per pole 1.3 W. The terminals accept stranded conductors up to 2 x 6 mm²; tightening torque is 1.3 Nm (12 lb-in); operating temperature is -25…+60 °C. It is used to select the speed of single-winding two-speed (Dahlander) motors.
| Series | C26 |
|---|---|
| Size Type | S1 |
| Function Code | A441 |
| Switch Function | Çift Devirli (1-0-2) |
| Switch Positions | 1-0-2 |
| Number of Positions | 3 |
| Switching Angle | 60° ° |
| Number of Poles | 3P |
| Number of Levels | 4 |
| Front Plate Code | F071 |
| Rated Current | 32 A |
| Conventional Free Air Thermal Current (Ith) | 32 A |
| Ambient temperature for rated current | 55 °C (24 hours, tepe 60 °C) |
| Conventional Enclosed Thermal Current (Ithe) | 32 A |
| Rated Insulation Voltage (Ui) | 690 V (AC 50/60 Hz) |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Overvoltage category | III |
| Pollution Degree | 3 |
| Rated Operational Current AC-15 (Ie) | 220–240 V: 14 A; 380–440 V: 6 A |
| Rated Operational Current AC-20A (Ie) | 690 V: 32 A |
| Rated Operational Current AC-21A (Ie) | 20–690 V: 32 A |
| Rated Operational Current AC-22A (Ie) | 220–500 V: 32 A; 660–690 V: 32 A |
| Rated Operational Power AC-2 (Pe) | 3-phase: 220–240 V 8 kW; 380–440 V 15 kW; 500 V 18.5 kW; 660–690 V 15 kW |
| Rated Operational Power AC-3 (Pe) | 3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 11 kW; 660–690 V 11 kW. 1-phase: 110–120 V 2.2 kW; 220–240 V 4 kW; 380–440 V 5.5 kW |
| Rated Operational Power AC-4 (Pe) | 3-phase: 220–240 V 2.7 kW; 380–440 V 5.5 kW; 500 V 5.5 kW; 660–690 V 5.5 kW. 1-phase: 110–120 V 0.75 kW; 220–240 V 1.5 kW; 380–440 V 3 kW |
| Rated Operational Power AC-23A (Pe) | 3-phase: 220–240 V 7.5 kW; 380–440 V 15 kW; 500 V 15 kW; 660–690 V 15 kW. 1-phase: 110–120 V 2.2 kW; 220–240 V 4 kW; 380–440 V 7.5 kW |
| Maximum Fuse Current | gG 50 A |
| Rated Short-Time Withstand Current (Icw) | 350 A (1 s) |
| Breaking Capacity | 220–240 V: 280 A; 380–440 V: 250 A; 660–690 V: 150 A |
| Power Loss per Pole | 1.3 W |
| Solid Conductor Cable Cross-Section | 1–6 mm2 |
| Stranded Conductor Cable Cross-Section | 2x6 mm2 |
| Flexible Conductor Cross-Section | 1.5–6 mm2 |
| Conductor Cross-Section with Ferrule | 1–4 mm2 |
| Cable section (AWG/MCM) | AWG 10 (flexible); AWG 8 (solid or stranded) |
| Conductor Material | Copper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered) |
| Tightening Torque | 1.3 Nm (12 lb-in) |
| Recommended Screw Driver | Pozidriv/Phillips PH2; slotted 1 x 5.5 mm (DIN 5264) |
| Contact Type | Rigid bridging link |
| Contact Material | Silver |