Kraus & Naimer CA20 A441/TRA301 Two-Speed (Dahlander) Cam Switch, 3-Pole, 25 A, in Enclosure (KE03)

Kraus & Naimer CA20 A441/TRA301 Two-Speed (Dahlander) Cam Switch, 3-Pole, 25 A, in Enclosure (KE03)

Kraus & Naimer CA20 A441/TRA301 is a 3-pole, 25 A two-speed (Dahlander) cam switch for single-winding motors. The switch has positions 1-0-2, a switching angle of 60° and 4 levels. It is supplied as an enclosed (TRA) version in a KE03 enclosure (IP65) with an I handle. Front plate code F071; size type S0. Rated insulation voltage is 690 V (AC 50/60 Hz) and rated impulse withstand voltage is 6 kV. AC-21A rated operational current is 25 A over 20–690 V; three-phase AC-3 rated power (380–440 V) is 7.5 kW; AC-23A rated power (380–440 V) is 11 kW. Maximum fuse rating gG 35 A; rated short-time withstand current 280 A (1 s); power loss per pole 0.9 W. The terminals accept stranded conductors up to 2 x 4 mm²; tightening torque is 1 Nm (9 lb-in); operating temperature is -25…+60 °C. It is used to select the speed of single-winding two-speed (Dahlander) motors.

SeriesCA20
Size TypeS0
Function CodeA441
Switch FunctionÇift Devirli (1-0-2)
Switch Positions1-0-2
Number of Positions3
Switching Angle60° °
Number of Poles3P
Number of Levels4
Front Plate CodeF071
Rated Current25 A
Conventional Free Air Thermal Current (Ith)25 A
Ambient temperature for rated current55 °C (24 hours, tepe 60 °C)
Conventional Enclosed Thermal Current (Ithe)25 A
Rated Insulation Voltage (Ui)690 V (AC 50/60 Hz)
Rated Impulse Withstand Voltage (Uimp)6 kV
Overvoltage categoryIII
Pollution Degree3
Rated Operational Current AC-15 (Ie)220–240 V: 8 A; 380–440 V: 5 A
Rated Operational Current AC-20A (Ie)690 V: 25 A
Rated Operational Current AC-21A (Ie)20–690 V: 25 A
Rated Operational Current AC-22A (Ie)220–500 V: 25 A; 660–690 V: 25 A
Rated Operational Power AC-2 (Pe)3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 15 kW; 660–690 V 13 kW
Rated Operational Power AC-3 (Pe)3-phase: 220–240 V 4 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 110–120 V 1.5 kW; 220–240 V 3 kW; 380–440 V 3.7 kW
Rated Operational Power AC-4 (Pe)3-phase: 220–240 V 1.5 kW; 380–440 V 3 kW; 500 V 3 kW; 660–690 V 3 kW. 1-phase: 110–120 V 0.45 kW; 220–240 V 1.1 kW; 380–440 V 2.2 kW
Rated Operational Power AC-23A (Pe)3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 11 kW; 660–690 V 11 kW. 1-phase: 110–120 V 1.5 kW; 220–240 V 3 kW; 380–440 V 5.5 kW
Maximum Fuse CurrentgG 35 A
Rated Short-Time Withstand Current (Icw)280 A (1 s)
Breaking Capacity220–240 V: 200 A; 380–440 V: 200 A; 660–690 V: 125 A
Power Loss per Pole0.9 W
Solid Conductor Cable Cross-Section0.75–4 mm2
Stranded Conductor Cable Cross-Section2x4 mm2
Flexible Conductor Cross-Section1.5–4 mm2
Conductor Cross-Section with Ferrule1–2.5 mm2
Cable section (AWG/MCM)AWG 12 (flexible); AWG 10 (solid or stranded)
Conductor MaterialCopper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered)
Tightening Torque1 Nm (9 lb-in)
Recommended Screw DriverPozidriv/Phillips PH1; slotted 0.8 x 5.5 mm (DIN 5264)
Contact TypeRigid bridging link
Contact MaterialSilver

Shipping & assurance

For made-to-order products, the procurement and carrier hand-over time is shared with the quotation.

In rare cases, all or part of an order may be unavailable due to stock or procurement updates. In this case, the customer is informed and the relevant product is cancelled and refunded. A product being open for sale does not guarantee that it is in physical store stock.

Delivery and returns