Kraus & Naimer C80 A310 Group Cam Switch, 1-Pole, 115 A, 88 x 88 mm Front Plate

Kraus & Naimer C80 A310 Group Cam Switch, 1-Pole, 115 A, 88 x 88 mm Front Plate

Kraus & Naimer C80 A310 is a 1-pole, 115 A group cam switch with 2 load groups and positions 0, A, A+B. Technical values: C80 type, size class S2, 88 x 88 mm front plate; thermal current Ith 115 A (55 °C), enclosed thermal current Ithe 115 A; rated insulation voltage Ui 690 V, rated impulse withstand voltage Uimp 6 kV; AC-21A 100 A, AC-22A 100 A, AC-13 230 V 50 A; maximum gG 125 A fuse, Icw 1300 A (1 s); conductor cross-section: solid 2.5–35 mm², flexible 6–25 mm²; tightening torque 4 Nm; 1 pole, 1 level, positions 0, A, A+B, switching angle 60°. Values are given in accordance with IEC 60947-3 and EN 60947-3. It is used to switch load groups A and B on in sequence: both groups are switched off in position 0, only group A is on in position A, and both groups are on in position A+B.

SeriesC80
Size TypeS2
Function CodeA310
Switch FunctionGrup Şalteri (0-A-A+B)
Switch Positions0-A-A+B
Number of Positions3
Switching Angle60° °
Number of Poles1P
Number of Levels1
Front Plate CodeF075
Front Plate Size (A x B)88 x 88 mm
Rated Current115 A
Conventional Free Air Thermal Current (Ith)115 A
Ambient temperature for rated current55 °C (24 hours, tepe 60 °C)
Conventional Enclosed Thermal Current (Ithe)115 A
Rated Insulation Voltage (Ui)690 V (AC 50/60 Hz)
Rated Impulse Withstand Voltage (Uimp)6 kV
Overvoltage categoryIII
Pollution Degree3
Rated Operational Current AC-13 (Ie)230 V: 50 A
Rated Operational Current AC-20A (Ie)690 V: 115 A
Rated Operational Current AC-21A (Ie)20–690 V: 100 A
Rated Operational Current AC-22A (Ie)220–500 V: 100 A; 660–690 V: 100 A
Rated Operational Power AC-2 (Pe)3-phase: 220–240 V 30 kW; 380–440 V 45 kW; 500 V 55 kW; 660–690 V 55 kW
Rated Operational Power AC-3 (Pe)3-phase: 220–240 V 15 kW; 380–440 V 30 kW; 500 V 30 kW; 660–690 V 30 kW. 1-phase: 110–120 V 3.7 kW; 220–240 V 7.5 kW; 380–440 V 13 kW
Rated Operational Power AC-4 (Pe)3-phase: 220–240 V 6 kW; 380–440 V 11 kW; 500 V 11 kW; 660–690 V 11 kW. 1-phase: 110–120 V 1.5 kW; 220–240 V 3 kW; 380–440 V 5.5 kW
Rated Operational Power AC-23A (Pe)3-phase: 220–240 V 30 kW; 380–440 V 45 kW; 500 V 55 kW; 660–690 V 45 kW. 1-phase: 110–120 V 5.5 kW; 220–240 V 15 kW; 380–440 V 22 kW
Maximum Fuse CurrentgG 125 A
Rated Short-Time Withstand Current (Icw)1300 A (1 s)
Breaking Capacity220–240 V: 860 A; 380–440 V: 860 A; 660–690 V: 400 A
Power Loss per Pole5.8 W
Solid Conductor Cable Cross-Section2.5–35 mm2
Stranded Conductor Cable Cross-Section35 mm2
Flexible Conductor Cross-Section6–25 mm2
Conductor Cross-Section with Ferrule4–25 mm2
Cable section (AWG/MCM)AWG 3 (flexible); AWG 2 (solid or stranded)
Conductor MaterialCopper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered)
Tightening Torque4 Nm (35 lb-in)
Recommended Screw DriverPozidriv/Phillips PH2; slotted 1.2 x 8 mm (DIN 5264)
Contact TypeRigid bridging link

Shipping & assurance

For made-to-order products, the procurement and carrier hand-over time is shared with the quotation.

In rare cases, all or part of an order may be unavailable due to stock or procurement updates. In this case, the customer is informed and the relevant product is cancelled and refunded. A product being open for sale does not guarantee that it is in physical store stock.

Delivery and returns