Kraus & Naimer CA20 A410 Star-Delta Cam Switch, 3-Pole, 25 A, 48 x 48 mm Front Plate
- Brand: Kraus & Naimer
- SKU: CA20 A410
- MPN: CA20 A410
- Model: 25 A
- Price: 3010.00 TRY + VAT · incl. VAT 3612.00 TRY
- Availability: In stock
- Star-Delta Switches
- Kraus & Naimer Star-Delta Switches
- Selection guide: What Is Star-Delta Connection? Switch Selection Guide
Kraus & Naimer CA20 A410 is a 3-pole, 25 A star-delta starting cam switch with 0-Y-Δ positions. Technical values: CA20 type, size class S0, 48 x 48 mm front plate; thermal current Ith 25 A (55 °C), enclosed thermal current Ithe 25 A; rated insulation voltage Ui 690 V, rated impulse withstand voltage Uimp 6 kV; AC-21A 25 A, AC-22A 25 A, AC-15 380–440 V 5 A; three-phase motor rating at 380–440 V: AC-3 7.5 kW, AC-23A 11 kW; maximum gG 35 A fuse, Icw 280 A (1 s); conductor cross-section: solid 0.75–4 mm², flexible 1.5–4 mm²; tightening torque 1 Nm; 3 poles, 4 levels, positions 0-Y-Δ, switching angle 60°. Values are given in accordance with IEC 60947-3 and EN 60947-3. It is used for star-delta starting of three-phase motors; the 0 position stops the motor.
| Size Type | S0 |
|---|---|
| Number of Poles | 3P |
| Series | CA20 |
| Function Code | A410 |
| Switch Function | Yıldız-Üçgen (0-Y-Δ) |
| Switch Positions | 0-Y-Δ |
| Number of Positions | 3 |
| Switching Angle | 60° ° |
| Number of Levels | 4 |
| Front Plate Code | F080 |
| Front Plate Size (A x B) | 48 x 48 mm |
| Rated Current | 25 A |
| Conventional Free Air Thermal Current (Ith) | 25 A |
| Ambient temperature for rated current | 55 °C (24 hours, tepe 60 °C) |
| Conventional Enclosed Thermal Current (Ithe) | 25 A |
| Rated Insulation Voltage (Ui) | 690 V (AC 50/60 Hz) |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Overvoltage category | III |
| Pollution Degree | 3 |
| Rated Operational Current AC-15 (Ie) | 220–240 V: 8 A; 380–440 V: 5 A |
| Rated Operational Current AC-20A (Ie) | 690 V: 25 A |
| Rated Operational Current AC-21A (Ie) | 20–690 V: 25 A |
| Rated Operational Current AC-22A (Ie) | 220–500 V: 25 A; 660–690 V: 25 A |
| Rated Operational Power AC-2 (Pe) | 3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 15 kW; 660–690 V 13 kW |
| Rated Operational Power AC-3 (Pe) | 3-phase: 220–240 V 4 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 110–120 V 1.5 kW; 220–240 V 3 kW; 380–440 V 3.7 kW |
| Rated Operational Power AC-4 (Pe) | 3-phase: 220–240 V 1.5 kW; 380–440 V 3 kW; 500 V 3 kW; 660–690 V 3 kW. 1-phase: 110–120 V 0.45 kW; 220–240 V 1.1 kW; 380–440 V 2.2 kW |
| Rated Operational Power AC-23A (Pe) | 3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 11 kW; 660–690 V 11 kW. 1-phase: 110–120 V 1.5 kW; 220–240 V 3 kW; 380–440 V 5.5 kW |
| Maximum Fuse Current | gG 35 A |
| Rated Short-Time Withstand Current (Icw) | 280 A (1 s) |
| Breaking Capacity | 220–240 V: 200 A; 380–440 V: 200 A; 660–690 V: 125 A |
| Power Loss per Pole | 0.9 W |
| Solid Conductor Cable Cross-Section | 0.75–4 mm2 |
| Stranded Conductor Cable Cross-Section | 2x4 mm2 |
| Flexible Conductor Cross-Section | 1.5–4 mm2 |
| Conductor Cross-Section with Ferrule | 1–2.5 mm2 |
| Cable section (AWG/MCM) | AWG 12 (flexible); AWG 10 (solid or stranded) |
| Conductor Material | Copper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered) |
| Tightening Torque | 1 Nm (9 lb-in) |
| Recommended Screw Driver | Pozidriv/Phillips PH1; slotted 0.8 x 5.5 mm (DIN 5264) |
| Contact Type | Rigid bridging link |
Shipping & assurance
Products in our store stock are handed over to the carrier on the same day, while products requiring procurement are generally handed over within 1–2 business days.
In rare cases, all or part of an order may be unavailable due to stock or procurement updates. In this case, the customer is informed and the relevant product is cancelled and refunded. A product being open for sale does not guarantee that it is in physical store stock.
Carrier hand-over cut-off
- Weekdays
- Saturday