Kraus & Naimer KG32B T203/09 VE Emergency Stop Main Switch, 3-Pole, 32 A, 64 x 64 mm Front Plate

Kraus & Naimer KG32B T203/09 VE Emergency Stop Main Switch, 3-Pole, 32 A, 64 x 64 mm Front Plate

Kraus & Naimer KG32B T203/09 VE is a 32 A (Ith), 3-pole emergency stop main switch (red handle, yellow front plate); base mounting with door clutch, 64 x 64 mm escutcheon plate, IP66/67. Ratings: rated insulation voltage Ui 690 V, impulse withstand voltage Uimp 6 kV, AC-21A 32 A, three-phase motor rating at 380–440 V: AC-3 7.5 kW, AC-23A 11 kW, breaking capacity 220 / 220 / 135 A (220–240 / 380–440 / 660–690 V), maximum fuse 35 A gG, short-time withstand current 430 A (1 s). Connection: flexible conductors 1.5–4 mm², solid or stranded conductors 0.75–6 mm², terminal tightening torque 1.25 Nm. Versions with door clutch are also supplied with a padlock device. The KG and C316 series switches exceed the requirements of IEC 60947-3 / EN 60947-3 (VDE 0660 part 107), IEC/EN 60204 and VDE 0113 and are used as switch disconnectors, main switches and maintenance switches.

Number of Poles3P
Rated Current32 A
Mounting TypeVE taban montajı, kapı kavramalı
IP RatingIP66/67
SeriesKG32B
Size TypeS00
Function CodeT203
Switch FunctionAcil Durdurma Fonksiyonlu Ana Şalter (0-1)
Switch Positions0-1
Number of Positions2
Front Plate Size (A x B)64 x 64 mm
Handle ColorRed (sarı ön plaka)
Conventional Free Air Thermal Current (Ith)32 A
Ambient temperature for rated current50 °C (24 hours, tepe 55 °C)
Conventional Enclosed Thermal Current (Ithe)32 A
Rated Insulation Voltage (Ui)690 V (AC 50/60 Hz)
Rated Impulse Withstand Voltage (Uimp)6 kV
Overvoltage categoryIII
Pollution Degree3
Rated Operational Current AC-20A (Ie)690 V: 32 A
Rated Operational Current AC-21A (Ie)20–690 V: 32 A
Rated Operational Current AC-22A (Ie)220–500 V: 32 A; 660–690 V: 32 A
Rated Operational Power AC-3 (Pe)3-phase: 220–240 V 5.5 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 220–240 V 3 kW; 380–440 V 5.5 kW
Rated Operational Power AC-23A (Pe)3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 11 kW; 660–690 V 11 kW. 1-phase: 220–240 V 4.2 kW; 380–440 V 7.5 kW
Maximum Fuse CurrentgG 35 A
Rated Short-Time Withstand Current (Icw)430 A (1 s)
Breaking Capacity220–240 V: 220 A; 380–440 V: 220 A; 660–690 V: 135 A
Power Loss per Pole1.1 W
Solid Conductor Cable Cross-Section0.75–6 mm2
Stranded Conductor Cable Cross-Section6 mm2
Flexible Conductor Cross-Section1.5–4 mm2
Conductor Cross-Section with Ferrule0.75–4 mm2
Cable section (AWG/MCM)AWG 10
Conductor MaterialCopper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered)
Tightening Torque1.25 Nm (11 lb-in)
Recommended Screw DriverPozidriv/Phillips PH2; slotted 0.8 x 4 mm (DIN 5264)
Contact TypeRigid bridging link
Contact MaterialSilver
Connection TypeScrew terminal
UL/CSA Rated Insulation Voltage (Ui)600 V AC