What Is a KNX/EIB Bus Cable? Types and Selection Criteria

An EIB-BUS (KNX) cable is a twisted-pair, foil-screened communication cable that links KNX sensors and actuators and carries both data and bus power.

Original Welibaba illustration of EIB-BUS Cables

An EIB-BUS cable (KNX cable) is a twisted-pair, foil-screened communication cable that connects sensors, push-buttons and actuators in the KNX building automation system, the successor of EIB. In homes, hotels and offices it carries both data and the devices' bus power over the same pair for lighting, blind and HVAC automation.

Types

Cables in the catalog

BrandSKUConstructionTypeCPR class
Reçber Kablo`501003`1x2x0.8+0.4 mmEIB BUS LSZHNot stated in name
Reçber Kablo`501046`1x2x0.8+0.4 mmKNX/EIB BUS LSZHB2ca
Reçber Kablo`501004`2x2x0.8+0.4 mmEIB BUS LSZHNot stated in name
Reçber Kablo`501045`2x2x0.8+0.4 mmKNX/EIB BUS LSZHB2ca
Mekas Kablo`11231`1x2x0.8+0.4 mm2Y(St)HNot stated in name
Mekas Kablo`11232`2x2x0.8+0.4 mm2Y(St)HNot stated in name
Erse Kablo`MDER014900200080L`2x2x0.8+0.4 mmEIB-H(St)HNot stated in name
Erse Kablo`MDER209300200080L`2x2x0.8+0.4 mmEIB-H(St)HB2ca-s1a,d1,a1
2M Kablo`3B12A156002-07A`2x2x0.8+0.4 mmYCYM-HFFRNot stated in name

0.8 mm is the core diameter; +0.4 mm is the drain wire that runs with the screen. The cables are sold by the metre.

Selection criteria

  1. KNX suitability: Choose a bus cable that the manufacturer states is suitable for the KNX line.
  2. Number of pairs: If you need a spare pair or a second line later, take 2x2x0.8 mm.
  3. Reaction-to-fire class: Choose a cable in the CPR class required by the building's fire regulations and the project specification.
  4. Line length: On a KNX TP line, the total cable length in one line must not exceed 1000 m, the distance between the power supply and a device 350 m, and between two devices 700 m.
  5. Installation: The minimum bending radius in the product data is 10 × cable diameter.

Common mistakes

Brands in the catalog

The EIB-BUS Cables category has 9 active products: Reçber Kablo 4, Mekas Kablo 2, Erse Kablo 2, 2M Kablo 1. Other bus and signal cables are in the Industrial and Communication Cables category.

Frequently asked questions

Are KNX cable and EIB-BUS cable the same?

Yes. EIB is the predecessor of KNX; the screened 2x2x0.8 mm or 1x2x0.8 mm bus cable used on a KNX TP line is sold under both names.

Which cores are used in a KNX cable?

The bus line is connected to the first pair: red (+), black (−). The second pair (white/yellow) is kept as a spare.

What does B2ca-s1a,d1,a1 mean?

It is a CPR reaction-to-fire class. B2ca gives the flame spread and heat release class, s1a low smoke density, d1 limited flaming droplets and a1 low acidity.

How long can a KNX line be?

The total cable length in one line must not exceed 1000 m. In larger installations a new line is added with a line coupler.