Fire Cables: J-H(St)H Halogen-Free Cable vs FE180 / PH120 Fire-Resistant Cable

How J-H(St)H fire alarm cable differs from FE180, PH120 and E30–E90 fire-resistant cables, what the IEC 60331 and EN 50200 tests prove, and which circuit needs which.

Two different properties are often confused in fire cables: not feeding the fire (halogen-free, flame retardant, low smoke) and continuing to work during the fire (circuit integrity). `J-H(St)H` offers the first; cables marked `FE180` / `PH120` add the second. The difference is defined by the IEC 60331 and EN 50200 tests.

> Related Category: Browse all types and sizes in Fire Cables, Fire-Resistant Cables and Fire Alarm Cables.

1. Reaction to fire vs resistance to fire

PropertyMeaningTestMarking
Halogen-freeNo corrosive acid gas when burningIEC 60754H, HFFR, LSZH
Low smokeEscape routes stay visibleIEC 61034LS, s1
Flame retardantFlame does not travel along the cableIEC 60332-1-2, 60332-3—
Insulation integrityConductors carry current under flame without shortingIEC 60331FE180
Circuit integrity with shockCircuit works under flame plus mechanical shockEN 50200PH30 / PH60 / PH90 / PH120
System functional integrityCable works together with its tray and clipsDIN 4102-12E30 / E60 / E90

The first three rows are reaction properties: the cable does not feed the fire but soon stops working. The last three are resistance properties, achieved with mica tape over the conductor or ceramifying silicone insulation.

2. What is J-H(St)H cable?

Code letters: `J` installation cable, `H` halogen-free insulation, `(St)` aluminium foil static screen with drain wire, `H` halogen-free sheath.

3. What do FE180, PH120 and E90 mean?

MarkingStandardTest conditionDurationWhat it proves
FE180IEC 60331Flame of at least 750 °C, no shock, cable alone180 minInsulation integrity
PH120EN 50200842 °C flame plus regular mechanical shock, cables ≤ 20 mm diameter120 min (PH30, PH60, PH90 also exist)Circuit integrity with shock
E30 / E90DIN 4102-12Furnace on the standard fire curve, cable + tray + clips together30 / 90 minThe installation working as a whole

4. Which cable for which circuit?

CircuitRequired propertyTypical cable
Addressable detection loop (detectors, call points)Halogen-free, screened; circuit integrity if specifiedJ-H(St)H or JE-H(St)H FE180, 1×2×0.8
Sounders, beacons, voice evacuationFire resistantJE-H(St)H FE180 PH120, screened 2×1 mm² and larger
Emergency lighting, fire pump, smoke extract fan, firefighter lift supplyFire-resistant power cableN2XH FE180 / E90
General lighting and sockets in public buildingsHalogen-free, low smokeN2XH, halogen-free wiring cables

National fire codes require fire resistance for cables of systems that must operate during a fire; the project specification sets the duration and class. Conductor size on alarm loops is verified by voltage drop from loop length and device current; long sounder lines need larger sizes such as 1×2×1.5 mm².

5. Installation notes

Frequently asked questions

Is J-H(St)H cable fire resistant?

No. Plain J-H(St)H is halogen-free and flame retardant but shorts quickly under flame. Fire resistance needs the JE-H(St)H type printed with FE180 and a PH or E class.

What is the difference between FE180 and PH120?

FE180 shows 180 minutes of insulation integrity in the IEC 60331 flame test without shock. PH120 shows 120 minutes of circuit integrity under 842 °C flame with mechanical shock per EN 50200 and is closer to real fire conditions.

Is halogen-free cable the same as fire-resistant cable?

No. Halogen-free cable emits no toxic, corrosive gas; fire-resistant cable keeps carrying current during a fire. All fire-resistant cables are halogen-free, but not the reverse.

What is the cross-section of 2×0.8 fire cable?

0.8 mm is the conductor diameter, about 0.5 mm². 2×2×0.8 means two pairs, that is four cores.

Why is fire alarm cable red?

The red sheath separates detection and alarm lines from other low-current cables. Fire-resistant types are usually orange or red; the print on the sheath, not the colour, is what counts.