Kraus & Naimer CA20B A007 Voltmeter Selector Switch, 25 A, 64 x 64 mm Front Plate
- Brand: Kraus & Naimer
- SKU: CA20B A007
- MPN: CA20B A007
- Model: 25 A
- Price: 2616.00 TRY + VAT · incl. VAT 3139.20 TRY
- Availability: Made to order
- Selector Step Switches
- Kraus & Naimer Selector Step Switches
- Selection guide: What Is a Selector Step Switch? Uses and Selection Criteria
Kraus & Naimer CA20B A007 is a 7-position voltmeter selector cam switch rated 25 A. The CA20B type switch has a 64 x 64 mm front plate (S0 switch with S1 size latching mechanism); Ith 25 A, Ui 690 V; rated short-time withstand current Icw is 280 A (1 s); terminals accept conductors up to 4 mm². Function: 7 positions (3 phase-to-phase + 0 + 3 phase-to-neutral), 45° switching angle, 3 stages. It is used to select and measure the phase-to-phase and phase-to-neutral voltages of a three-phase system with a single voltmeter.
| Series | CA20B |
|---|---|
| Size Type | S1 |
| Function Code | A007 |
| Switch Function | Voltmetre Komütatörü (L1-L2, L2-L3, L3-L1, 0, L1-N, L2-N, L3-N) |
| Switch Positions | L1-L2, L2-L3, L3-L1, 0, L1-N, L2-N, L3-N |
| Number of Positions | 7 |
| Switching Angle | 45° ° |
| Number of Levels | 3 |
| Front Plate Code | F782 |
| Front Plate Size (A x B) | 64 x 64 mm |
| Rated Current | 25 A |
| Conventional Free Air Thermal Current (Ith) | 25 A |
| Ambient temperature for rated current | 55 °C (24 hours, tepe 60 °C) |
| Conventional Enclosed Thermal Current (Ithe) | 25 A |
| Rated Insulation Voltage (Ui) | 690 V (AC 50/60 Hz) |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Overvoltage category | III |
| Pollution Degree | 3 |
| Rated Operational Current AC-15 (Ie) | 220–240 V: 8 A; 380–440 V: 5 A |
| Rated Operational Current AC-20A (Ie) | 690 V: 25 A |
| Rated Operational Current AC-21A (Ie) | 20–690 V: 25 A |
| Rated Operational Current AC-22A (Ie) | 220–500 V: 25 A; 660–690 V: 25 A |
| Rated Operational Power AC-2 (Pe) | 3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 15 kW; 660–690 V 13 kW |
| Rated Operational Power AC-3 (Pe) | 3-phase: 220–240 V 4 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 110–120 V 1.5 kW; 220–240 V 3 kW; 380–440 V 3.7 kW |
| Rated Operational Power AC-4 (Pe) | 3-phase: 220–240 V 1.5 kW; 380–440 V 3 kW; 500 V 3 kW; 660–690 V 3 kW. 1-phase: 110–120 V 0.45 kW; 220–240 V 1.1 kW; 380–440 V 2.2 kW |
| Rated Operational Power AC-23A (Pe) | 3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 11 kW; 660–690 V 11 kW. 1-phase: 110–120 V 1.5 kW; 220–240 V 3 kW; 380–440 V 5.5 kW |
| Maximum Fuse Current | gG 35 A |
| Rated Short-Time Withstand Current (Icw) | 280 A (1 s) |
| Breaking Capacity | 220–240 V: 200 A; 380–440 V: 200 A; 660–690 V: 125 A |
| Power Loss per Pole | 0.9 W |
| Solid Conductor Cable Cross-Section | 0.75–4 mm2 |
| Stranded Conductor Cable Cross-Section | 2x4 mm2 |
| Flexible Conductor Cross-Section | 1.5–4 mm2 |
| Conductor Cross-Section with Ferrule | 1–2.5 mm2 |
| Cable section (AWG/MCM) | AWG 12 (flexible); AWG 10 (solid or stranded) |
| Conductor Material | Copper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered) |
| Tightening Torque | 1 Nm (9 lb-in) |
| Recommended Screw Driver | Pozidriv/Phillips PH1; slotted 0.8 x 5.5 mm (DIN 5264) |
| Contact Type | Rigid bridging link |
| Contact Material | Silver |
Shipping & assurance
For made-to-order products, the procurement and carrier hand-over time is shared with the quotation.
In rare cases, all or part of an order may be unavailable due to stock or procurement updates. In this case, the customer is informed and the relevant product is cancelled and refunded. A product being open for sale does not guarantee that it is in physical store stock.