Switch and Circuit Breaker Types: MCCB vs Load Break Switch vs ACB vs Motor Protection Breaker

Moulded case breakers, air circuit breakers, motor protection breakers, load break switches, cam and transfer switches compared; breaker vs disconnector, Icu, Ics and pole choice.

A switch opens and closes an electrical circuit by hand or automatically. The first question in selection is whether the device only switches and isolates, or also protects by tripping on overcurrent and short circuit. Devices that protect are circuit breakers (IEC 60947-2); those that do not are load break switches and switches (IEC 60947-3).

> Related Category: Browse all types and ratings in Switches, Molded Case Circuit Breakers and Load Break Switches.

1. Switch types compared

TypeCurrent rangeProtectionUse
Moulded case circuit breaker (MCCB)16–1,600 AOverload + short circuitMain and sub-board incomers, feeders
Air circuit breaker (ACB)630–6,300 AElectronic, adjustable, selectiveTransformer output, main switchboard incomer
Motor protection circuit breaker (MPCB)0.1–100 AAdjustable thermal + magnetic, phase lossProtection and manual control of one motor
Load break switch16–3,150 ANoneOn-load switching, isolation for maintenance
Fuse switch-disconnector32–1,250 ABy NH fusesFused protection instead of an MCCB
Cam switch10–200 ANoneMachine main switch, 0-1, 1-0-2, star-delta
Transfer switch16–3,200 ANone (used with breakers)Mains–generator changeover; manual or automatic
Modular switch16–125 ANoneDIN-rail isolation and control inside boards

2. What is an MCCB?

A circuit breaker in a moulded insulating case holding contacts and trip unit together. It trips by itself on overload and short circuit and is reset once the fault is cleared.

Trip unitAdjustmentUse
Thermal-magnetic, fixedNoneSmall feeders
Thermal-magnetic, adjustableThermal 0.7–1 × In, magnetic 5–10 × InGeneral distribution
ElectronicLong, short and instantaneous settings plus earth faultIncomers needing selectivity, generators

The toggle has three positions: on, off and a middle trip position. After a trip, pull the toggle fully down to reset, then close. For the difference from a miniature breaker see MCB vs MCCB Circuit Breaker Difference.

3. Air circuit breakers

Open-type power circuit breakers for high currents have a metal frame, stored-energy spring mechanism and usually a withdrawable design. They can carry short-circuit current for a set time (0.5–1 s) without tripping, letting the downstream breaker clear the fault first. This is the short-time withstand current (Icw) and is the basis of selectivity.

4. Load break switch vs circuit breaker

PropertyLoad break switchCircuit breaker (MCCB, ACB)
Switches rated currentYesYes
Breaks short-circuit currentNoYes
Trips by itself on overcurrentNoYes
Visible or reliable isolating positionYesOn types suitable for isolation
Needs upstream protectionYes (fuse or breaker)No

A load break switch isolates a circuit safely for maintenance and its handle can be padlocked. As it gives no protection, a fuse or breaker must always sit upstream. Fused versions combine protection and isolation; fuse types are covered in Fuse Types.

5. Motor protection, cam and transfer switches

6. Selection criteria

CriterionMeaningRule
In (rated current)Current carried continuouslyLoad current ≤ In ≤ cable current-carrying capacity
Icu (ultimate breaking capacity)Highest short-circuit current it can breakAbove the prospective fault current at the point of installation
Ics (service breaking capacity)Current after which it stays in service; 25–100% of IcuPrefer Ics = 100% Icu on incomers
Icw (short-time withstand)Current and time carried without trippingUpstream levels where selectivity is required
Poles3P or 4P4P in TT and generator systems where the neutral must be isolated

Frequently asked questions

What is an MCCB?

A moulded case circuit breaker. It trips by itself on overload and short circuit across 16–1,600 A and is used on board incomers and large feeders.

What is the difference between an MCCB and a load break switch?

An MCCB breaks short-circuit current and protects. A load break switch only switches rated current and isolates for maintenance; it cannot break a short circuit and needs a fuse or breaker upstream.

When is an air circuit breaker used?

On main incomers above 630 A and at transformer and generator outputs. Its short-time withstand rating gives selectivity with downstream breakers, and the withdrawable design eases maintenance.

Should a breaker be 3-pole or 4-pole?

Use 4 poles where the neutral must be isolated with the phases: TT systems, mains–generator changeover and incomers with residual current protection. Use 3 poles in TN-C systems where the neutral is not switched.

What do Icu and Ics mean?

Icu is the highest short-circuit current the breaker can interrupt once. Ics is the current after which it can remain in service, given as a percentage of Icu.