Kraus & Naimer C26 A246 8-Step Cam Switch with OFF, 1-Pole, 32 A, 64 x 64 mm Front Plate

Kraus & Naimer C26 A246 8-Step Cam Switch with OFF, 1-Pole, 32 A, 64 x 64 mm Front Plate

Kraus & Naimer C26 A246 is a 1-pole step cam switch with 8 steps and an OFF (0) position; thermal current 32 A, front plate size 64 x 64 mm. The handle of the C26 A246 turns in 30° steps through the positions 0-1-2-3-4-5-6-7-8, and each position engages a different contact arrangement; number of levels 4, front plate code F006. It is used in multi-position selection and control circuits. For C26 A246, rated insulation voltage Ui is 690 V, AC-21A rated current is 32 A, maximum fuse rating is gG 50 A and rated short-time withstand current Icw is 350 A (1 s). C26 A246 is connected by screw terminals: flexible conductors of 1.5–6 mm², conductors with ferrule of 1–4 mm² and stranded conductors of 2 x 6 mm² can be connected; tightening torque is 1.3 Nm.

Size TypeS1
Number of Poles1P
Cam Switch Position Count8 Positions
SeriesC26
Function CodeA246
Switch FunctionStepped With Off (0-1-2-3-4-5-6-7-8)
Switch Positions0-1-2-3-4-5-6-7-8
Number of Positions9
Switching Angle30° °
Number of Levels4
Front Plate CodeF006
Front Plate Size (A x B)64 x 64 mm
Rated Current32 A
Conventional Free Air Thermal Current (Ith)32 A
Ambient temperature for rated current55 °C (24 hours, tepe 60 °C)
Conventional Enclosed Thermal Current (Ithe)32 A
Rated Insulation Voltage (Ui)690 V (AC 50/60 Hz)
Rated Impulse Withstand Voltage (Uimp)6 kV
Overvoltage categoryIII
Pollution Degree3
Rated Operational Current AC-15 (Ie)220–240 V: 14 A; 380–440 V: 6 A
Rated Operational Current AC-20A (Ie)690 V: 32 A
Rated Operational Current AC-21A (Ie)20–690 V: 32 A
Rated Operational Current AC-22A (Ie)220–500 V: 32 A; 660–690 V: 32 A
Rated Operational Power AC-2 (Pe)3-phase: 220–240 V 8 kW; 380–440 V 15 kW; 500 V 18.5 kW; 660–690 V 15 kW
Rated Operational Power AC-3 (Pe)3-phase: 220–240 V 5.5 kW; 380–440 V 11 kW; 500 V 11 kW; 660–690 V 11 kW. 1-phase: 110–120 V 2.2 kW; 220–240 V 4 kW; 380–440 V 5.5 kW
Rated Operational Power AC-4 (Pe)3-phase: 220–240 V 2.7 kW; 380–440 V 5.5 kW; 500 V 5.5 kW; 660–690 V 5.5 kW. 1-phase: 110–120 V 0.75 kW; 220–240 V 1.5 kW; 380–440 V 3 kW
Rated Operational Power AC-23A (Pe)3-phase: 220–240 V 7.5 kW; 380–440 V 15 kW; 500 V 15 kW; 660–690 V 15 kW. 1-phase: 110–120 V 2.2 kW; 220–240 V 4 kW; 380–440 V 7.5 kW
Maximum Fuse CurrentgG 50 A
Rated Short-Time Withstand Current (Icw)350 A (1 s)
Breaking Capacity220–240 V: 280 A; 380–440 V: 250 A; 660–690 V: 150 A
Power Loss per Pole1.3 W
Solid Conductor Cable Cross-Section1–6 mm2
Stranded Conductor Cable Cross-Section2x6 mm2
Flexible Conductor Cross-Section1.5–6 mm2
Conductor Cross-Section with Ferrule1–4 mm2
Cable section (AWG/MCM)AWG 10 (flexible); AWG 8 (solid or stranded)
Conductor MaterialCopper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered)
Tightening Torque1.3 Nm (12 lb-in)
Recommended Screw DriverPozidriv/Phillips PH2; slotted 1 x 5.5 mm (DIN 5264)