Kraus & Naimer C42 A252 5-Step Cam Switch without OFF, 2-Pole, 63 A, 64 x 64 mm Front Plate
- Brand: Kraus & Naimer
- SKU: C42 A252
- MPN: C42 A252
- Model: 63 A
- Price: 7574.00 TRY + VAT · incl. VAT 9088.80 TRY
- Availability: Made to order
- Standard Step Switches
- Kraus & Naimer Standard Step Switches
- Selection guide: Standard Step Switches Selection Guide
Kraus & Naimer C42 A252 is a 2-pole step cam switch with 5 steps and no OFF position; thermal current 63 A, front plate size 64 x 64 mm. The handle of the C42 A252 turns in 60° steps through the positions 1-2-3-4-5, and each position engages a different contact arrangement; number of levels 5, front plate code F078. It is used in multi-position selection and control circuits. For C42 A252, rated insulation voltage Ui is 690 V, AC-21A rated current is 63 A, maximum fuse rating is gG 80 A and rated short-time withstand current Icw is 1000 A (1 s). Single-phase AC-3 motor rating is 6 kW at 220–240 V and 11 kW at 380–440 V. C42 A252 is connected by screw terminals: flexible conductors of 4–10 mm², conductors with ferrule of 2.5–10 mm² and stranded conductors of 2 x 16 mm² can be connected; tightening torque is 3 Nm.
| Size Type | S1 |
|---|---|
| Number of Poles | 2P |
| Cam Switch Position Count | 5 Positions |
| Series | C42 |
| Function Code | A252 |
| Switch Function | Stepped Without Off (1-2-3-4-5) |
| Switch Positions | 1-2-3-4-5 |
| Number of Positions | 5 |
| Switching Angle | 60° ° |
| Number of Levels | 5 |
| Front Plate Code | F078 |
| Front Plate Size (A x B) | 64 x 64 mm |
| Rated Current | 63 A |
| Conventional Free Air Thermal Current (Ith) | 63 A |
| Ambient temperature for rated current | 55 °C (24 hours, tepe 60 °C) |
| Conventional Enclosed Thermal Current (Ithe) | 63 A |
| Rated Insulation Voltage (Ui) | 690 V (AC 50/60 Hz) |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV (circuit breaker); 4 kV (switch-disconnector) |
| Overvoltage category | III |
| Pollution Degree | 3 |
| Rated Operational Current AC-15 (Ie) | 220–240 V: 16 A; 380–440 V: 7 A |
| Rated Operational Current AC-20A (Ie) | 690 V: 63 A |
| Rated Operational Current AC-21A (Ie) | 20–690 V: 63 A |
| Rated Operational Current AC-22A (Ie) | 220–500 V: 63 A; 660–690 V: 63 A |
| Rated Operational Power AC-2 (Pe) | 3-phase: 220–240 V 18.5 kW; 380–440 V 30 kW; 500 V 40 kW; 660–690 V 37 kW |
| Rated Operational Power AC-3 (Pe) | 3-phase: 220–240 V 11 kW; 380–440 V 18.5 kW; 500 V 18.5 kW; 660–690 V 18.5 kW. 1-phase: 110–120 V 3 kW; 220–240 V 6 kW; 380–440 V 11 kW |
| Rated Operational Power AC-4 (Pe) | 3-phase: 220–240 V 5.5 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 110–120 V 1.2 kW; 220–240 V 2.4 kW; 380–440 V 4 kW |
| Rated Operational Power AC-23A (Pe) | 3-phase: 220–240 V 15 kW; 380–440 V 30 kW; 500 V 45 kW; 660–690 V 40 kW. 1-phase: 110–120 V 4 kW; 220–240 V 10 kW; 380–440 V 18.5 kW |
| Maximum Fuse Current | gG 80 A |
| Rated Short-Time Withstand Current (Icw) | 1000 A (1 s) |
| Breaking Capacity | 220–240 V: 550 A; 380–440 V: 550 A; 660–690 V: 365 A |
| Power Loss per Pole | 1.7 W |
| Solid Conductor Cable Cross-Section | 1.5–16 mm2 |
| Stranded Conductor Cable Cross-Section | 2x16 mm2 |
| Flexible Conductor Cross-Section | 4–10 mm2 |
| Conductor Cross-Section with Ferrule | 2.5–10 mm2 |
| Cable section (AWG/MCM) | AWG 6 |
| Conductor Material | Copper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered) |
| Tightening Torque | 3 Nm (26.4 lb-in) |
| Recommended Screw Driver | Pozidriv/Phillips PH3; slotted 1.6 x 8 mm (DIN 5264) |
Shipping & assurance
For made-to-order products, the procurement and carrier hand-over time is shared with the quotation.
In rare cases, all or part of an order may be unavailable due to stock or procurement updates. In this case, the customer is informed and the relevant product is cancelled and refunded. A product being open for sale does not guarantee that it is in physical store stock.